EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 17.3.5 For Any XY Pair (2 oo2)

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Brüel & Kjaer Vibro S1079330.002 / V04 Page 123 of 188
Technical alterations reserved!
Brüel & Kjaer Vibro Instruction
VC-8000 MPS
Content
EN
17.3.5 For Any XY Pair (2oo2)
The ‘For Any XY Pair (2oo2)’ block performs the logical AND functions across the two channels in an
XY pair and then the logical OR function across all pairs in the group.
Channels X and Y must be UMM channels 1,2 (or 3,4) and have the same channel type. This is
called a channel pair. All paired channels in the selected asset group (“With: The Rack”, or “With:
Motor A”) are included in this logic.
Channel B
Channel A
Danger
Fault
Bypass
Danger
True
True
True
Fault
True
False
False
Bypass
True
False
False
Table 17-8) "For any XY Pair Dependent" truth table
This block performs as follows:
1. Logical AND function between the two
channels in the XY pair. This is called “2 out
of 2”. For example: (1X and 1Y).
2. Logical OR function between other pairs in
the selected asset group. For example: (1X
and 1Y) or (2X and 2Y) or (3X and 3Y) or
3. Bypassed channels are removed from the
logic. For example, If Channel 1X is bypassed the relay logic ((1X and 1Y) or (2X and 2Y)) will
become ((1Y) or (2X and 2Y)).
4. Faulted channels are removed from the logic. For example, If Channel 1X is faulted the relay
logic ((1X and 1Y) or (2X and 2Y)) will become ((1Y) or (2X and 2Y)). If both Channels 1X and
1Y are faulted the relay logic becomes (2X and 2Y).
1 2 3 4 5
Brg 1X
Danger
Danger
Danger
Danger
Bypass
Brg 1Y
Danger
Bypass
Fault
Ok
Bypass
Brg 2X
Ok
Ok
Ok
Danger
Danger
Brg 2Y
Ok
Ok
Ok
Ok
Ok
Relay Active True True True False False
Table 17-9) ‘For Any XY Pair (2oo2)’ scenarios
Figure
17-9) For Any XY Pair (2oo2 Enforced)

Table of Contents