To create a register with packed status bits.
Copy the status registers (rows) in the Modbus map to the 3x or 4x register section.
Enter the new register address (i.e. 30501)
Enter the new Bit field 1 thru 16
Figure 21-8) Address and bit settings for packed status registers
21.6.6 Read Current Values
The channel value can be read from either Input Registers (3x) or Holding Registers (4x). The value
can be read as a 32-bit floating point value, or as a scaled value (0 to 65535). B&K Vibro
recommends using the floating-point value if it is supported by your DCS system.
Format Description
32-bit floating point
Value is read in actual engineering units (i.e. 2.5
mils)
16-bit unsigned integer
Value is read as a scaled value (percentage) (i.e. 0
to 10 mils = 0 to 65535, or 0 to 4095).
For example: Current value = 2.5 mils,
Measurement range is 0 to 10 mils (2.5 mils =
25%), Modbus range =
0-4095. Modbus Value (25%) = 1023.
Data provided as 32 Bit Floating point values use two 16-bit registers. The word order can be
swapped (see section 21.3.5)