23.8 License Upgrades
Be aware. This procedure may trip relays. Do not perform this procedure unless all relays are
externally bypassed, or the machine is down.
You should also
Notify Operations that data will be temporarily lost, relays may change state, and
the OK relay may change state.
Action Screen Capture
Install the latest version of VC-8000 MPS
Open VC-8000 Rack Maintenance software
Connect to the rack.
A local connection does not require a
password for license updates.
Save a Rack Maintenance file.
Email the file to B&K Vibro Technical Support
requesting a license update.
Please reference the purchase order.
The support request will take up to 24 hours.
A license update file will be emailed to you.
The file extension is “.setk”
Select the Firmware Upgrade Tab.
Select Enable Hardware
Select the license update file. The file
extension is “.setk”.
Look for a message in the lower left corner of
the software, indicating that “Hardware support
activation is complete”