24.1.2 Axial Position
Typical uses: thrust position
Measurement Description Configuration
Axial Position
Measures the position change in the axial direction.
Commonly used for thrust position measurements.
Default
Gap
DC sensor Gap voltage for diagnostics.
Default
Axial Vibration
Band-pass filtered Peak-Peak displacement
-6dB/octave (1 pole) roll-on, roll-off
Add (if needed)
24.1.3 Axial Position with Sync
Typical uses: thrust position with Phase Trigger association.
Measurement Description Default or Add
Axial Position
Measures the position change in the axial direction.
Commonly used for thrust position measurements.
Default
Gap
DC sensor Gap voltage for diagnostics.
Default
Axial Vibration
Band-pass filtered Peak-Peak displacement
-6dB/octave (1 pole) roll-on, roll-off
Add (if needed)
24.1.4 Phase Trigger
Typical uses: tachometer, Keyphasor ®
Measurement Description Default or Add
Speed
Rotational speed.
Default
Gap
The average Gap voltage for diagnostics.
Default
Rotor
Acceleration
Change in rotational speed
Add (if needed)
Peak Speed
Maximum speed reached since the peak speed was reset.
Add (if needed)
24.1.5 Radial Vibration
Typical uses: Radial Vibration on fluid film bearings using proximity probes.
Measurement Description Default or Add
Direct
Overall dynamic amplitude measurement.
6 dB/octave (1 pole) roll-on, -6 dB/octave (1 pole) roll-off.
Default
Gap
DC sensor Gap voltage for diagnostics.
Default
1X amplitude
and phase
A synchronous amplitude and phase measurement at
running speed.
Default
Requires PT
2X amplitude
and phase
A synchronous amplitude and phase measurement at twice
running speed.
Default
Requires PT
nX
An additional synchronous amplitude and phase
measurement at the configured multiple of running speed.
Commonly used for 0.5X or 3X measurements.
Default
Requires PT
Band-pass 1
An additional Peak-Peak bandpass filtered measurement.
Add this band-pass filter to filter a different region, change
units or subunits, or provide additional alarms.
Add (if needed)
Band-pass 2
An additional Peak-Peak bandpass filtered measurement.
Add this band-pass filter to filter a different region, change
units or subunits, or provide additional alarms.
Add (if needed)