24.2.3 Aero-Derivative Velocity
Typical uses: Aero-Derivative Gas Turbines with Aero Interface Modules using Band Pass Filters
Measurement Description Default or Add
Band-pass
Band-pass filtered dynamic amplitude measurement.
Commonly used for a narrow band velocity measurement.
-48 dB/octave (8 pole) roll-on, roll-off.
Default
Band-pass
Band-pass filtered dynamic amplitude measurement. May
be used for a wideband velocity measurement.
-48 dB/octave (8 pole) roll-on, roll-off.
Default
Bias
DC sensor bias for diagnostics.
Default
24.3 Diagnostic Channels
Diagnostic channels are standard channel types but with default settings typical for a Machinery
Diagnostic Services (MDS) engineer using a portable VC-8000 system (for high speed data
collection) and connected to the buffered output of an existing protection system.
24.3.1 Diagnostic Proximity (Radial Vibration)
Same measurements as the standard Radial Vibration Channel
24.3.2 Diagnostic Velocity
Same measurements as the standard Velocity channel.
24.3.3 Diagnostic Acceleration
Same measurements as the standard Acceleration channel.
24.3.4 General Dynamic
Typical uses: Basic (undefined) channel type for large voltage range +/- 24 Vdc or special
circumstances (like for special sensor and unit i.e. a current clamp and Amps).
Measurement Description Default or Add
Direct
Overall dynamic amplitude measurement.
24 dB/octave (4 pole) roll-on, -24 dB/octave (4 pole) roll-off.
Default
Bias
DC sensor bias voltage for diagnostics.
Default
24.4 Hydro and Low Speed Machines
24.4.1 Accel Slow RMS
Typical uses: Vibration monitoring with a slower RMS detector.
Measurement Description Default or Add
Direct
Overall dynamic amplitude measurement. RMS value
calculated over a 30-s interval.
24 dB/octave (4 pole) roll-on, -24 dB/octave (4 pole) roll-off.
Default
Bias
DC sensor bias voltage for diagnostics.
Default