Page 172 of 188
█ © Brüel & Kjaer Vibro ● S1079330.002 / V04
Technical alterations reserved
EN
24.4.2 Air Gap
Typical uses: Air Gap measurements on hydro turbine generators.
Measurement Description Default or Add
Minimum Air
The measured minimum Air Gap updated each revolution.
DC sensor bias voltage for diagnostics.
24.4.3 Hydro Radial Vibration
Typical uses: Hydro turbines or other low speed machines with proximity transducers. Maximum
speed 720 rpm.
Measurement Description Default or Add
Direct
Overall dynamic amplitude measurement.
84 dB /octave (14 pole) roll-on, -72 dB/octave (12 pole) roll-
DC sensor Gap or bias voltage for diagnostics.
1X Amplitude
A synchronous amplitude measurement at running speed.
Requires PT
2X Amplitude
A synchronous amplitude measurement at twice running
speed.
Requires PT
24.4.4 Hydro Velocity
Typical uses: Hydro turbines or other low speed machines with velocity transducers. Maximum
speed 720 rpm.
Direct
Overall dynamic amplitude measurement.
84 dB /octave (14 pole) roll-on, -72 dB/octave (12 pole) roll-
DC sensor bias voltage for diagnostics.
1X Amplitude
A synchronous amplitude measurement at running speed.
Requires PT
2X Amplitude
A synchronous amplitude measurement at twice running
speed.
Requires PT
24.4.5 Low Frequency Acceleration
Typical uses: Fans or other low speed machinery.
Measurement Description Default or Add
Direct
Overall dynamic amplitude measurement. Integrating
results in velocity. The Low Frequency acceleration
channel can be configured for integration as low as 1 Hz.
24 dB/octave (4 pole) filter roll-on, -24 dB/octave (4 pole)
Bandpass
Addable bandpass measurement. Can be integrated to
provide integrated and non-integrated measurements
DC sensor bias voltage for diagnostics.