24.11.7 Eccentricity
Typical uses: Steam turbine eccentricity
Measurement Description Default or Add
Peak to peak eccentricity measurement.
DC sensor Gap voltage for diagnostics.
Min
The minimum position measured during a single shaft
rotation.
Max
The maximum position measured during a single shaft
rotation.
Ecc Position
The shaft position. Below the crossover speed Ecc Position
is the instantaneous measured position. Above the
crossover speed Ecc Position is the average position.
24.11.8 Shaft Absolute RV
Typical uses: Shaft vibration measurements where the absolute casing vibration is large. Also used
as replacement for shaft-riders.
Measurement Description Default or Add
Shaft Abs
Summation of the relative direct with the integrated case
velocity to obtain the absolute vibration displacement.
Direct
Shaft relative overall dynamic amplitude measurement.
6 dB/octave roll-on, -6 dB/octave roll-off.
DC sensor Gap voltage for diagnostics.
1X amplitude
Shaft relative synchronous amplitude and phase
measurement at running speed.
24.11.9 Shaft Absolute Vel
Typical uses: Shaft vibration measurements where the absolute casing vibration is large. Also used
as replacement for shaft-riders.
Measurement Description Default or Add
Velocity Direct
Casing velocity dynamic amplitude measurement.
24 dB/octave (4 pole) roll-on, -24 dB/octave (4 pole) roll-off
Intg Direct
Casing velocity integrated to displacement dynamic
amplitude measurement. Used in the Shaft Absolute
calculation
24 dB/octave (4 pole) roll-on, -24 dB/octave (4 pole) roll-off
DC sensor bias voltage for diagnostics
1X amplitude
Casing velocity integrated to displacement synchronous
amplitude and phase measurement at running speed
24.11.10 Valve Position
Typical uses: Steam turbine valve position measurement using an AC LVDT and transmitter.
Measurement Description Default or Add
Measures the valve % open or % closed
The sensor bias voltage for diagnostics