25 Other MPS Features (less used)
25.1 Simulated Phase Triggers
Use a simulated Phase Trigger (PT) under the following
conditions only.
No physical speed sensor is installed.
Your machine runs at a constant speed.
1X, 2X, nX amplitudes (at running speed) are
needed.
Synchronous waveform (at running speed) is
needed
Create simulated PT from the Channels tab, Phase Trigger
view: Click “Add” and select simulated phase trigger:
Simulated Phase Triggers will be shown in the list of available Phase Triggers (Channels Tab,
Summary View) where they can be associated with a vibration channel.
Simulated Phase Triggers:
Do not consume a channel
Always show the simulated speed (even when machine is stopped)
Do not have alarm or fault statuses
Do not show as a bar graph on the VC-8000 front panel
Cannot be used as a phase reference (associated channels will have invalid phase)
Show on the display detail views
Show in CMS
Are not synchronized between UMMs
IMPORTANT!
A simulated phase trigger channel will always show the configured speed value
(i.e. 3600 RPM) - even when the machine is not running.