1.2.1 Rack Connection Module (RCM)
The Rack Connection Module (RCM) installs
in slot 1 and provides rack power
connections and other rack level interfaces.
Primary power input
Secondary power input
Discrete contact control inputs
Rack Fault Relay
Reset button
LED indictors
Buffered transducer outputs
1.2.1.1 Redundant Power Supplies
The VC-8000 rack requires +24 Vdc external
power to operate. Redundant power inputs
are provided.
Plant +24 Vdc power can also be used.
IMPORTANT
+24Vdc COM is not isolated from the
Signal COM (in the UMM).
When using plant power (+24 Vdc), a
24V to 24V isolator is necessary.
Refer to the datasheets for information on
external power supply hardware, input
voltage tolerance, and current requirements.
Figure 1-3) RCM
Buffered Out
connector to external
device
+24 Vdc power input
connectors (2 pos)
Status LEDs
Latched Status Reset
Pushbutton
Discrete control contacts
(to dry relay contacts or
+5V TTL logic)
Fault Relay Contacts.
NC closes on fault
(or power loss)