9.3.3 Modbus Discrete Input Commands
Modbus commands can be used to set
the Reset, Inhibit, Trip Multiply, or SAI
commands at the rack level only; for
example, you cannot use Modbus
commands to place a “Machine Group”
into Trip Multiply.
To use a Modbus command, Allow Status
Register Writes must be enabled in the
SAM Modbus settings.
Figure 9-11) Allow Modbus write commands
9.3.4 VC-8000 Rack Maintenance Software Commands
The VC-8000 Rack Maintenance Software can be used to reset the rack, bypass a signal channel, or
bypass a relay channel.
To bypass a signal (or relay) channel, connect to the rack (local USB, or Remote), select the channel
(or relay), and then select Enable Bypass. The channel will remain bypassed until the user selects
Disable Bypass.
Figure9-12) Bypass a channel
Enable Bypass is not possible from the touch screen display. You must connect to the rack
with a PC and run the VC-8000 Rack Maintenance software.