Table 3 Superheat Charging -- AC Only
OUTDOOR TEMP (_F)
EVAPORATOR ENTERING AIR TEMPERATURE (_FWB)
50 52 54 56 58 60 62 64 67 68 70 72 74 76
55 9 12 14 17 20 23 26 29 32 35 37 40 42 45
60 7 10 12 15 18 21 24 27 30 33 35 38 40 43
65 6 10 13 16 19 21 24 27 30 33 36 38 41
70 7 10 13 16 19 21 24 27 30 33 36 39
75 6 9 12 15 18 21 24 28 31 34 37
80 5 8 12 15 18 21 25 28 31 35
85 8 11 15 19 22 26 30 33
90 5 9 13 16 20 24 27 31
95 6 10 14 18 22 25 29
100 8 12 15 20 23 27
105 5 9 13 17 22 26
110 6 11 15 20 25
115 8 14 18 23
*Optimum performance point, 95_F(35_C) outdoor ambient and (80_F/27_C dry bulb), (67_F/19_C wet bulb) indoor conditions. (DOE A Test Conditions)
Where a dash (--- --- ) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.
Note: Superheat _F is at low--- side service port, Allow a tolerance of ±3_F(±1.7_C)
Note: Indoor dry bulb between 70_Fand80_F(21_Cand27_C)
Table 4 Required Suction --Line Temperature
SUPERHEAT TEMP (_F)
SUCTION PRESSURE AT SERVICE PORT (PSIG)
107.8 112.2 116.8 121.2 126 130.8 138.8 140.8 145.8
0 35 37 39 41 43 45 47 49 51
2 37 39 41 43 45 47 49 51 53
4 39 41 43 45 47 49 51 53 55
6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59
10 45 47 49 51 53 55 57 59 61
12 47 49 51 53 55 57 59 61 63
14 49 51 53 55 57 59 61 63 65
16 51 53 55 57 59 61 63 65 67
18 53 55 57 59 61 63 65 67 69
20 55 57 59 61 63 65 67 69 71
22 57 59 61 63 65 67 69 71 73
24 59 61 63 65 67 69 71 73 75
26 61 63 65 67 69 71 73 75 77
28 63 65 67 69 71 73 75 77 79
30 65 67 69 71 73 75 77 79 81
32 67 69 71 73 75 77 79 81 83
34 69 71 73 75 77 79 81 83 85
36 71 73 75 77 79 81 83 85 87
38 73 75 77 79 81 83 85 87 89
40 75 77 79 81 83 85 87 89 91