m. Dry bulb outdoor air temperature sensor shall
be provided as standard. Enthalpy sensor is also
available on factory-installed economizers only.
Outdoor air sensor setpoint shall be adjustable
and shall range from 40°F to 100°F (4°C to
38°C). Additional sensor options shall be avail-
able as accessories.
n. The economizer controller shall also provide
control of an accessory power exhaust unit
function. Factory set at 100%, with a range of
0% to 100%.
o. The economizer shall maintain minimum air-
flow into the building during occupied period
and provide design ventilation rate for full
occupancy.
p. Dampers shall be completely closed when the
unit is in the unoccupied mode.
q. Economizer controller shall accept a 2 to 10 Vdc
CO
2
sensor input for IAQ/DCV control. In this
mode, dampers shall modulate the outdoor air
damper to provide ventilation based on the sen-
sor input.
r. Compressor lockout temperature on W7220
control is adjustable from –45°F to 80°F (–43°C
to 27°C), set at a factory default of 32°F (0°C).
W7212 control opens at 35°F (2°C) and closes
at 50°F (10°C).
s. Actuator shall be direct coupled to economizer
gear. No linkage arms or control rods shall be
acceptable.
t. Economizer controller shall provide indications
when in free cooling mode, in the DCV mode,
or the exhaust fan contact is closed.
2. Integrated EconoMi$er
®
2, and EconoMi$er X
Ultra Low Leak rate models. (Factory-installed on
3 phase models only. Field-installed on all 3 and 1
phase models):
a. Integrated, gear driven opposing modulating
blade design type capable of simultaneous
economizer and compressor operation.
b. Independent modules for vertical or horizontal
return configuration shall be available. Vertical
return modules shall be available as a factory
installed option.
c. Damper blades shall be galvanized steel with
composite gears. Plastic or composite blades on
intake or return shall not be acceptable.
d. Shall include all hardware and controls to pro-
vide free cooling with outdoor air when tem-
perature and/or humidity are below setpoints.
e. Shall be equipped with gear driven dampers for
both the outdoor ventilation air and the return
air for positive air stream control.
f. Ultra Low Leak design meets California
Title 24 section 140.4 and ASHRAE 90.1
requirements for 4 cfm per sq ft on the outside
air dampers and 10 cfm per sq ft on the return
dampers.
g. Economizer controller on EconoMi$er X models
shall be the Honeywell W7220 that provides:
1) 2-line LCD interface screen for setup, con-
figuration and troubleshooting.
2) On-board Fault Detection and Diagnostics
(FDD) that senses and alerts when the
economizer is not operating properly, per
California Title 24, ASHRAE 90.1 and
IECC.
3) Sensor failure loss of communication iden-
tification.
4) Automatic sensor detection.
5) Capabilities for use with multiple-speed
indoor fan systems.
6) Utilize digital sensors: Dry bulb and
Enthalpy.
h. Economizer controller on EconoMi$er 2 models
with RTU Open controls shall be a 4 to 20mA
design controlled directly by the controller. RTU
Open meets California Title 24, ASHRAE 90.1
and IECC Fault Detection and Diagnostic (FDD)
requirements.
i. Shall be capable of introducing up to 100% out-
door air.
j. Shall be equipped with a barometric relief
damper capable of relieving up to 100% return
air and contain seals that meet ASHRAE 90.1
requirements.
k. Shall be designed to close damper(s) during
loss-of-power situations with spring return built
into motor.
l. Dry bulb outdoor air temperature sensor shall
be provided as standard. Enthalpy sensor is also
available on factory-installed economizers only.
Outdoor air sensor setpoint shall be adjustable
and shall range from 40°F to 100°F (4°C to
38°C). Additional sensor options shall be avail-
able as accessories.
m. The economizer controller shall also provide
control of an accessory power exhaust unit
function. Factory set at 100%, with a range of
0% to 100%.
n. The economizer shall maintain minimum air-
flow into the building during occupied period
and provide design ventilation rate for full
occupancy.
o. Dampers shall be completely closed when the
unit is in the unoccupied mode.
p. Economizer controller shall accept a 2 to 10 vdc
CO
2
sensor input for IAQ/DCV control. In this
mode, dampers shall modulate the outdoor air
damper to provide ventilation based on the sen-
sor input.
q. Compressor lockout temperature on W7220
control is adjustable from –45°F to 80°F (–43°C
to 27°C), set at a factory default of 32°F (0°C).
W7212 control opens at 35°F (2°C) and closes
at 50°F (10°C).
Guide specifications (cont)