General parameters
9
Logamatic 4323 - Subject to technical modifications.
39
Press "Back" to return to the next level up.
Turn the rotary selector until submenu "Temp. contr 10V equates to" appears.
Hold down "Display" and turn the rotary selector until the required set value
appears (here: "90°C").
The display shows the set value.
Release "Display" to save your input.
+
GENERAL PARAM.
90°C
10V equates to
Temp. contr
Input range Factory setting
Temperature control 0 V
5 °C99 °C 5 °C
Temperature control 10 V
5 °C99 °C 90 °C
USER INFORMATION
If a curve with a negative incline is programmed, e.g. 0 V = 90 °C, ensure that
all 0 – 10
V inputs of a control unit are controlled. An open input corresponds
to 0
V and thus to a heat demand of, for example, 90 °C.
The demand should be set parallel at all inputs of a control unit, if applicable.