EasyManua.ls Logo

Buderus Logamatic 4323 - Setting Switching Optimisation

Buderus Logamatic 4323
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Heating circuit data
11
Logamatic 4323 - Subject to technical modifications.
59
11.16Setting switching optimisation
The function "Optimisation for" is not enabled at the factory.
Install a remote control with room temperature sensor to enable
the
"Optimisation" function.
The following variations are possible:
Heat-up commences before the actual switching time, if "Start" has been
selected.
The control unit calculates the start time so that the set room temperature is
achieved at the set start point.
At "Stop" the system begins setback, where possible prior to the actual
setback time to save energy. If a room cools down unexpectedly or suddenly,
the stop optimisation is terminated and heating continues normally up to
the
programmed setback time.
Both optimisation versions are used when "Start/Stop" has been enabled.
Switching optimisation is not implemented if "none" is selected.
Call up the service level. "Gen. parameters" is shown as the first main menu.
Turn the rotary selector until the main menu "Heating circ. + no." appears
(here:
"Heating circ. 2").
Press "Display" to call up a submenu (here: "Heating system").
USER INFORMATION
As the start optimisation is limited to 240 minutes, start optimisation
is
frequently inappropriate for systems with a long heat-up time.
+
+

Table of Contents

Other manuals for Buderus Logamatic 4323

Related product manuals