ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 27 of 48
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
REPLACE/ADD DEVICE
This function may be used, for example, to replace a faulty loop device, or add a new loop device.
NB: THIS MENU OPTION HAS TO BE SELECTED BEFORE A LOOP DEVICE IS
REPLACED OR ADDED.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Replace/Add Device.
When the REPLACE/ADD DEVICE prompt is displayed press the Accept 4 button.
Select which loop (1 or 2) to replace or add a device using the using the scroll 5 button then press
the Accept4button.
Note: Loop 1 has been selected in the following example.
Select the device address using the 5and6scroll buttons, as shown below:
Press the Accept4button and the following display appears:
Note: If you do not want to proceed at this point, you
may exit this function by pressing the Escape 3button.
Replace or add the selected loop device to an empty base.
The panel will now auto-address the new device as address 10.
Press the Escape 3button x 3 and the panel will perform a learning process.
Note: If the panel requests the NVM link to be fitted continue onto the following steps.
When requested by the panel fit the NVM link shown below:
The panel perform a loop learn and the following summary is displayed:
Press the Accept 4button and the Escape 3button. Remove the NVM link when requested by the panel.
Loop : 1
112 Devices Found
Auto learn complete, Press Accept
Loop : 1 Device : 10
Loop : 1 Device : 10
Waiting for device
Please fit the NVM Link now
Remove NVM Un-Lock Link