ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 28 of 48
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CHANGE ADDRESS
This function is used to change device addresses at the panel, therefore saving the use of ladders to
access a device on site.
Note: The CAPROG Handheld Programmer can be used to manually change the address of a device, but
this will also require a loop learn to be carried out.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Change Address.
When the CHANGE ADDRESS prompt is displayed press the Accept 4button.
Select which loop (1 or 2) to change an address using the scroll 5 button then press the Accept4button.
Note: Loop 1 has been selected in the following example and the following is displayed:
Enter the address you want to change using the 5and6scroll buttons then press the Accept 4button.
The device’s LED will light and the following is displayed, for example ‘Device 8’.
Enter the new address of the device using the 5and6scroll buttons, for example ‘Device 9’, then press
the Accept 4button.
In this example the panel will auto-assign address 8 to address 9.
When requested by the panel fit the NVM link shown below:
Wait until the old address is flashing, address 8 is shown below.
Press the Escape 3button x 4. The panel will re-learn the loop. Wait for the process to complete and
a brief summary window will appear, similar to the one shown below:
Press the Accept4button then press the Escape 3button to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
Loop : 1 Device : 8
New Address : 8
Loop : 1 Device : 8
New Address : 9
Please fit the NVM Link now
112 Devices Found
Auto learn complete, Press Accept
6: 50 16 Jan : Normal
Remove the NVM Un-Lock link