Page 10 - Manual FA02007-IT - 11/2023 - © CAME S.p.A. - The contents of this manual may be changed, at any time, and without notice. - Original instructions
Functions menu
Start programming by first running the following functions: Motor type, Number of motors, TOTAL
STOP and self-learning.
DIP-SWITCH Description of functions
Motor type
By default, the control panel controls OPP001 and FTL20DGC-series gearmotors.
For controlling OPS001, BXL04AGS-series gearmotors.
select the DIP-switches as shown and press the PROG button on the control board. The LED stays lit and the
buzzer sounds once.
To return to the default setting, press PROG again. The LED flashes and the buzzer sound
s off twice.
Number of motors
By default, two motors are configured.
To configure a single motor:
select the DIP-switches as shown and press the PROG button on the control board. The LED stays lit and the
buzzer sounds once.
To return to the default setting, press PROG again. The LED flashes and the buzzer sounds off twice.
TOTAL STOP from button (contact 1-2)
By default, the feature is enabled.
To disable it:
select the DIP-switches as shown and press the PROG button on the control board. The LED flashes and the
buzzer sounds off twice.
To return to the default setting, press PROG again. The LED stays lit and the buzzer sounds once.
Self-learning of the gate travel (see Self-learning paragraph)
Select the DIP-switches as shown and press the PROG button on the control board.
The operator will perform a series of maneuvers to establish the limit-switch points. To establish the slow-
down staring points - when opening and closing - press PROG when the gate leaves reach the desired
position.
During calibration the PRG LED flashes. Once the calibration is done the buzzer sounds off once.
If the calibration is not successful, the LED flashes quickly and the buzzer sounds off seven times.
You can interrupt the gate travel's self-learning operation by pressing the STOP button (if enabled).
Reopening during closing (contact 2-C1)
By default, the feature is disabled.
To enable it:
select the DIP-switches as shown and press the PROG button on the control board. The LED stays lit and the
buzzer sounds once.
To return to the default setting, press PROG again. The LED flashes and the buzzer sounds off twice.
Input on contact 2-CX
By default, the feature is disabled.
To enable it:
select the DIP-switches as shown and press the PROG button on the control board. The LED stays lit and the
buzzer sounds once.
To return to the default setting, press PROG again. The LED flashes and the buzzer sounds off twice.
Partial stop or obstruction wait (contact 2-CX)
By default, the function is set to partial stop.
To enable theobstruction wait:
Select the DIP-switches as shown and press the PROG button on the control board. The LED stays lit and
the buzzer sounds once.
To return to the default setting, press PROG again. The LED flashes and the buzzer sounds off twice.
OPEN-CLOSE-INVERT or OPEN-STOP-CLOSE-STOP from button (contact 2-7)
By default, the feature is OPEN-CLOSE-INVERT.
To enable it to OPEN-STOP-CLOSE-STOP:
select the DIP-switches as shown and press the PROG button on the control board. The LED stays lit and the
buzzer sounds once.
To return to the default setting, press PROG again. The LED flashes and the buzzer sounds off twice.