P. 9 - Manual code: 319V21EN Vers. 3 04/2017 © CAME cancelli automatici S.p.A. - The data and information in this manual are subject to change at any time without prior notice required by Came Cancelli Automatici S.p.A.
ENGLISH
At each opening and closing command, the control board assesses the e ciency status of the safety devices (photocells). Any
anomaly found is signaled with the fl ashing of the LED on the control board. Consequently it cancels any commands coming from
the transmitter or the button.
Electrical connection to enable the photocell safety test:
- the transmitter and the receiver, must be connected as per the diagram;
- from the “F5” function select which inputs to run the safety test on.
Electrical connection for running the photocells safety test
DF with monitoring card
for DFI connections.
Confi gure either (N.C.) contacts CX or CY,
input for safety devices such as sensate
edges, that comply with
EN 12978 standards. See CX (F2 Function)
or CY(F3 Function) input functions in:
- C7 «re-open while closing», during gate
closing, opening the contact causes inver-
sion of movement until gate is fully open;
- C8 «re-close while opening», during gate
opening, opening the contact causes inver-
sion of movement until gate is fully close.
N.B. : if CX and CY contacts are unused
they need to be deactivated during
programming.