GEARMOTORS WITHOUT R INTERFACE (control board 119RIR267)
A1 - Motor type
0 = Generic
F46 - Number of motors
A2 - Motor test
> open the M2 leaf
< open the M1 leaf
Check that both leaves open. If they do not, invert M and N on the relevant terminal.
F2 - CX input
F3 - CY input
F72 - Limit-switch function
2 = Slowdown (Default)
Select the parameter if both microswitches are used for slowdown.
3 = Opening limit-switch, closing slowdown
Select the parameter if the opening microswitch is used as a limit switch.
F73 - Input type FC/FA
0 = N.O. (Default)
Select the parameter if both microswitches are normally open.
2 = N.C. for FA input, N.O. for FC input
Select the parameter if the closing microswitch is normally open and the opening microswitch is normally closed.
A8 - Motor power
2 = Medium power (Default) [up to 200W]
3 = Maximum power [more than 200W]
F39 - M1 opening approach point
F40 - M1 closing approach point
F43 - Opening approach point for M2
F44 - Closing approach point for M2
Set a value below 5%
F35 - Slowdown AST control
100%
A3 - Travel calibration
If “A1” scrolls across the display, this means the type of motor must be set before any other parameters can be modifi ed.