Index Parameter Description
Ed02
Unit 1
Unit 2
-
-
Unit 20
Add unit to the Master/Slave system.
To add a unit to the network enter the unit’s IP address. Scroll between
the units using the UP/DOWN buttons
Ed03
Maximum production
of Master/Slave
system. Unitrotation
Set maximum production of the Master/Slave system.
Load: this is the maximum capacity effectively required for the
Master/Slave system, settable by the user.
Maximum: this is the sum of the maximum capacities of the units
added to the Master/Slave system
Set the unit rotation logic.
Rotation: Grouped (Default), Balanced
Ed04
Advanced
preheating
Rotation time
Enable the advanced preheating function for Master/Slave systems.
Possible settings: YES/NO
Set the auto-rotation time between units
Possible settings: 0-65535 hours (Default 3 hours).
If auto-rotation time = 0 the function is disabled.
Ed05 Offline timeout
Set the offline time for units in the Master/Slave system
Range: 500-1000 ms
Ed06
Disconnect unit from
Master/Slave system
Disconnect the current unit from the Master/Slave system
Possible settings: YES/NO
Remarks: this disconnects and removes the current unit from the
Master/Slave system.
Display Master/Slave system production.
Index Parameter Description
Ed07
Master/Slave
production
Display the request (%) and the production (kg/h / lbs/h) of the
Master/Slave system
Display unit status and the percentage of production for each unit in the Master/Slave system:
Index Parameter Description
Ed08 Display Master/ Slave system Unit status with corresponding % of production
Ed09
Display info on individual
unit.
Unit 1, Unit 2, ...,Unit 20
Display unit operating hours, current production and any alarms
To move between the various units use the UP/DOWN arrows
The display is available for each unit
Maintenance on the units in the Master/Slave system:
Index Parameter Description
Ed10 Unit switched-off for maintenance Unit switched off to carry out maintenance.
For detailed information on the Master/Slave system, see the chapter Master/Slave system”.
7.6
Menu E. Settings
- e. Backup
7.6.1 Enable backup unit (Installer menu)
In some critical applications where relative humidity control is very important, it may be essential have a
backup unit available in the event of malfunctions on the main unit. To enable the backup unit, go to
screen Ee01:
Index Parameter Description
Ee01 Enable backup
Enable automatic unit backup in the event of shutdown, using a
second independent unit
Default: Disabled
Possible settings: Enabled/Disabled
ENG
gaSteam - UG +0300090EN rel. 1.2 09.10.2018
7. User menu and unit configuration|77