31
ENG
“heaterSteam” +0300080EN - rel. 1.0 - 27.04.2016
Menu Screen Menu description Menu type Controller type
E. Settings
(password)
c. Confi guration SSR PWM period Ec23 Duration of SSR modulation period Installer heaterSteam process
heaterSteam titanium
d. Master/Slave Master/Slave Ed01 Initial Master/Slave system confi guration
Press “PRG” to confi gure the Master/Slave network
Installer heaterSteam titanium
Unit 1
Unit 2 . . . Unit 20
Ed02 Add unit to the Master/Slave system Installer heaterSteam titanium
Maximum production of
Master/Slave system.
Unit rotation.
Ed03 Set maximum production of the Master/Slave system
Set the unit rotation logic
Installer heaterSteam titanium
Advanced preheating
Rotation time.
Ed04 Enable the advanced preheating function for Master/Slave
systems
Set the rotation time between one unit and the next
Installer heaterSteam titanium
Offl ine timeout. Ed05 Set the unit offl ine time in the Master/Slave system Installer heaterSteam titanium
Disconnect unit from
Master/Slave system
Ed06 Disable/disconnect the current unit from the Master/Slave
system
Installer heaterSteam titanium
Master/Slave production Ed07 Display the request (%) and the production (kg/h / lbs/h) of the
Master/Slave system
Press “PRG” to confi gure the Master/Slave network
Installer heaterSteam titanium
Display Master/Slave
system
Ed08 Unit status with corresponding % of production
Press “PRG” to confi gure the Master/Slave network
Installer heaterSteam titanium
Display info on individual
unit. Unit 1 Unit 2 . ..
Unit 20
Ed09 Display unit operating hours, current production and any alarms
To move between the various units use the UP and DOWN
arrows
Installer heaterSteam titanium
Unit switched off for
maintenance.
Ed10 Unit switched off for maintenance Installer heaterSteam titanium
e. Backup Enable backup Ee01 Enable automatic unit backup in the event of shutdown, using a
second independent unit
Installer heaterSteam titanium
Priority when starting Ee02 Defi ne the priority of the units when in backup mode Installer heaterSteam titanium
f. Manual mode Type of manual mode Ef01 Enable manual mode: Disabled, manual management of
outputs and manual request
Service Installer heaterSteam process
heaterSteam titanium
Manual management of
outputs
Ef02 Test the outputs: fi ll valve, drain pump, contactor, SSR status, SSR
ON time, SSR OFF time
Service Installer heaterSteam process
heaterSteam titanium
Manual management of
request
Ef03 Manually set the production request Service Installer heaterSteam process
heaterSteam titanium
g. Initialisation Wizard Eg01 Start the wizard for initial unit confi guration
Set whether to display the wizard when next restarting
Service Installer heaterSteam process
heaterSteam titanium
Language Eg02 Set the language Service Installer heaterSteam process
heaterSteam titanium
Unit of measure and lan-
guage when starting
Eg03 Set unit of measure (International or Imperial).
Select the language when starting
Installer heaterSteam process
heaterSteam titanium
Change password Eg04 Change the password (Service, Installer). Service Installer heaterSteam process
heaterSteam titanium
Inst. default Eg06 Unit factory reset. Important: resetting the model will cancel all
of the control settings and load the default values
Service Installer heaterSteam process
heaterSteam titanium
Software update Eg07 Update the unit software from USB pen drive Service Installer heaterSteam process
heaterSteam titanium
Export parameters Eg08 Export the confi guration parameters from the unit to USB pen
drive
Service Installer heaterSteam process
heaterSteam titanium
Import parameters Eg09 Import the confi guration parameters from USB pen drive to
the unit
Service Installer heaterSteam process
heaterSteam titanium
h. Supervision Unit supervision address
on BMS port
Eh01 Set the unit address for supervision. Enable the supervisor type
and protocol
Installer heaterSteam process
heaterSteam titanium
BMS port communication
settings
Eh02 Set the communication parameters for supervision via BMS:
Baud rate, stop bits and parity
Installer heaterSteam process
heaterSteam titanium
BACnet MS/TP
confi guration
Eh03 Set the address, maximum number of masters and maximum
number of frames
Installer heaterSteam process
heaterSteam titanium
Ethernet network settings Eh04 Set DHCP, IP address, mask, gateway, DNS for the Ethernet
network. Important: these values must be provided by the local
network administrator
Installer heaterSteam process
heaterSteam titanium
Supervision settings on
Ethernet port
Eh05 Select the protocol on the Ethernet port: ModBus or BACnet Installer heaterSteam process
heaterSteam titanium
i. Logout Logout Ei01 Information on the type of login performed. Possibility to logout Service Installer heaterSteam process
heaterSteam titanium
Tab. 6.e
6.14 Alarms
Any active alarms will be shown on the corresponding screen with direct
access from the display.
When an alarm occurs, the corresponding alarm button
starts fl ashing.
In these conditions, pressing the alarm button
once displays the type
of alarm. In the event of potentially dangerous alarms, the humidifi er
automatically stops steam production. For certain alarm events, as well as
the alarm signal, the alarm relay is activated (see Chap. 13 “Alarm table”).
When the cause of the alarm is no longer present:
• the humidifi er and the alarm relay are reset automatically or manually;
• the message shown on the display can only be cleared manually (see
Chap. 13 “Alarm table”);
Even if no longer active, the alarm status continues to be indicated until
“clear display” button is pressed.
Alarms that are still active cannot be reset. If there is more than one alarm,
the display shows all the alarms in sequence.
From the alarm screen, the alarm log can be displayed by pressing “Enter”
. For the complete table of alarms, see chapter 13. Alarm table.