Digital variables
Variable Variable name R/W Description Category
1 RemOn R Remote on/off I/O
2 ThermPtcDin R Thermal DIN status
3 LevSenStatus.Low R Level sensor: low level
4 LevSenStatus.Hi R Level sensor: high level
5 LevSenStatus.Foam R High level sensor: foam
6 OnOff Status R Unit status On or OFF On/Off
7 OnBySV RW Start command from SV (Supervisor)
13 PreMaintWarn R Maintenance pre-alert (not an alarm) Alarms
14 CurrBlkAlrm.IsBlocker R Shutdown alarm
15 CurrBlkAlrm.IsPresent R Resettable alarm
16 CurrBlkAlrm.Warning R Warning
17 Alrm_Autotest.Active R Autotest alarm
18 Alrm_HighConductAl.Active R High conductivity alarm
19 Alrm_LevSen.Active R Level sensor broken alarm
20 Alrm_ThermPtc.Active R Thermal overload alarm
21 Alrm_Wmiss.Active R No water alarm
22 Alrm_LowProd.Active R Low production alarm
23 Alrm_MainPrb.Active R Main probe fault alarm
24 Alrm_LimPrb.Active R Limit probe fault alarm
25 Alrm_PreHPrb.Active R NTC preheating probe fault alarm
26 Alrm_HiHum.Active R High humidity alarm
27 Alrm_LoHum.Active R Low humidity alarm
28 Alrm_HiHumLim.Active R High humidity limit alarm
29 Alrm_Foam.Active R Foam alarm
30 Alrm_PeriodicMaint.Active R Periodical maintenance request
31 Alrm_CylFull.Active R Cylinder full alarm
32 Alrm_ConductPrb.Active R Conductivity probe fault alarm
33 Alrm_HighConductWr.Active R High conductivity warning
34 Alrm_RetMem.Active R Retain memory damaged warning
35 Warn_Autotest.Active R Autotest warning
36 Warn_LevSen.Active R Level sensor warning
37 Warn_LowProd.Active R Low production warning
38 Alrm_WirelessPrb_1_Offl ine.Active R Wireless probe 1 offl ine
39 Alrm_WirelessPrb_2_Offl ine.Active R Wireless probe 2 offl ine
40 Alrm_WirelessPrb_3_Offl ine.Active R Wireless probe 3 offl ine
41 Alrm_WirelessPrb_4_Offl ine.Active R Wireless probe 4 offl ine
42 Alrm_MissingModel.Active R Model not confi gured
43 Alrm_NetUnit_1.Active R Active alarm on unit 1
44 Alrm_NetUnit_2.Active R Active alarm on unit 2
45 Alrm_NetUnit_3.Active R Active alarm on unit 3
46 Alrm_NetUnit_4.Active R Active alarm on unit 4 Alarms
47 Alrm_NetUnit_5.Active R Active alarm on unit 5
48 Alrm_NetUnit_6.Active R Active alarm on unit 6
49 Alrm_NetUnit_7.Active R Active alarm on unit 7
50 Alrm_NetUnit_8.Active R Active alarm on unit 8
51 Alrm_NetUnit_9.Active R Active alarm on unit 9
52 Alrm_NetUnit_10.Active R Active alarm on unit 10
53 Alrm_NetUnit_11.Active R Active alarm on unit 11
54 Alrm_NetUnit_12.Active R Active alarm on unit 12
55 Alrm_NetUnit_13.Active R Active alarm on unit 13
56 Alrm_NetUnit_14.Active R Active alarm on unit 14
57 Alrm_NetUnit_15.Active R Active alarm on unit 15
58 Alrm_NetUnit_16.Active R Active alarm on unit 16
59 Alrm_NetUnit_17.Active R Active alarm on unit 17
60 Alrm_NetUnit_18.Active R Active alarm on unit 18
61 Alrm_NetUnit_19.Active R Active alarm on unit 19
62 Alrm_NetUnit_20.Active R Active alarm on unit 20
63 Alrm_WirelessPrb_1_LowBatt.Active R Wireless probe 1: Low battery level alarm
64 Alrm_WirelessPrb_2_LowBatt.Active R Wireless probe 2: Low battery level alarm
65 Alrm_WirelessPrb_3_LowBatt.Active R Wireless probe 3: Low battery level alarm
66 Alrm_WirelessPrb_4_LowBatt.Active R Wireless probe 4: Low battery level alarm
67 Alrm_WirelessPrb_Main.Active R Wireless probe fault (main group)
68 Alrm_WirelessPrb_Limit.Active R Wireless probe fault (limit group)
69 SchedDayCfg[0].EnTB RW Scheduler: Enable band 1 Scheduler
70 SchedDayCfg[1].EnTB RW Scheduler: Enable band 2
71 SchedDayCfg[2].EnTB RW Scheduler: Enable band 3
72 SchedDayCfg[3].EnTB RW Scheduler: Enable band 4
73 SchedDayCfg[4].EnTB RW Scheduler: Enable band 5
74 SchedDayCfg[5].EnTB RW Scheduler: Enable band 6
Tab. 11.d
Note: for existing supervisors, a table has been created for backward
compatibility, contact Carel for the list (Carel retro).