“heaterSteam +0300080EN - rel. 1.0 - 27.04.2016
Alarm Cause Possible solution Reset Alarm relay Action
Cylinder full
warning
Cylinder full of water to the high level
sensor on the cover, without humidifi -
cation request
Check the fi ll valve for leaks
Check whether the high level sensor is dirty
Check that there is no condensate return along the steam
pipe
Automatic Open Signal only
Conductivity meter
warning
Conductivity meter not connected or
damaged
Check the connection of the conductivity meter for measu-
ring feedwater conductivity
Manual Open Stop
production
Controller memory
damaged warning
Problem in the electronic controller Replace the controller Automatic Open Signal only
Wireless probe 1
offl ine
No communication with probe 1 Check binding between probe and access point, check the
battery. Check the probe signal level.
Automatic Closed Signal only
Wireless probe 2
offl ine
No communication with probe 2 Check binding between probe and access point, check the
battery. Check the probe signal level.
Automatic Closed Signal only
Wireless probe 3
offl ine
No communication with probe 3 Check binding between probe and access point, check the
battery. Check the probe signal level.
Automatic Closed Signal only
Wireless probe 4
offl ine
No communication with probe 4 Check binding between probe and access point, check the
battery. Check the probe signal level.
Automatic Closed Signal only
No model Model not set Set a model Automatic when is
selected the model
Closed Stop
production
Network alarm on
unit 1
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 2
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 3
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 4
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 5
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 6
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 7
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 8
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 9
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 10
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 11
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 12
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 13
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 14
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 15
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 16
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 17
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 18
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 19
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Network alarm on
unit 20
Network unit alarm (see the specifi ed
unit for details)
Carry out the checks based on the alarm displayed on the
unit in question
Automatic Open Signal only
Wireless probe 1
battery
Battery discharged on wireless probe 1 Check battery charge, replace if necessary; Automatic Open Signal only
Wireless probe 2
battery
Battery discharged on wireless probe 2 Check battery charge, replace if necessary; Automatic Open Signal only
Wireless probe 3
battery
Battery discharged on wireless probe 3 Check battery charge, replace if necessary; Automatic Open Signal only
Wireless probe 4
battery
Battery discharged on wireless probe 4 Check battery charge, replace if necessary; Automatic Open Signal only
Main wireless
probe group not
working
All the main probes wireless are not
operate
Check probe connections and binding to the access point Stop - automatic Closed Stop
production
Limit wireless
probe group not
working
All the limit probes wireless are not
operate
Check probe connections and binding to the access point Stop - automatic Closed Stop
production
Tab. 13.a