+0300085EN rel. 2.2 - 07.05.2019
Action Troubleshooting
/ Check correct compressor operation (presence of liquid, excessive refrigerant charge, compressor sizing,..)
Evaporators with valves fully open at the same time (e.g. MOP set incorrectly on MPXPRO, valves stuck open,..)
Compressor shutdown, set on Cae27 Check correct compressor operation (incorrect sizing, low refrigerant charge,..)
Evaporators with valves closed and compressors running (valves stuck closed,..)
LT compressor and parallel compressor shutdown Check the two level sensors (low, high)
Check wiring and electrical panel connections
Check DI confi guration
Compressor shutdown Check BLDC compressor operation based on the type of alarm
Type of alarm signalled settable on screen Cae02
Compressor shutdown Check BLDC compressor operation based on the type of alarm
Type of alarm signalled settable on screen Cae05
Parallel compressor shutdown Check parallel compressor operation based on the type of alarm
Type of alarm signalled settable on screen Cbe02
Parallel compressor shutdown Check parallel compressor operation based on the type of alarm
Type of alarm signalled settable on screen Cbe05
Compressor shutdown, settable
on Hc06
Check circuit piping
Check refrigerant charge level in the circuit
Compressor shutdown and fan on
settable on Hc05
Check piping, valves and circuit components
Check correct compressor operation
One or both fans shut down, depending on the
confi guration
Check fan connections and correct fan operation
Fan sizing not suitable for the system
Excessive refrigerant charge in the circuit
Actions involving the clock no longer confi gured
Unit shutdown Change board
/ Check the set probe *
/ Check the set probe *
/ Check the set probe *
/ Check the set probe *
/ Check the set probe *
/ Check the set probe *
/ Check operating hour threshold on screen Cac13
Reset operating hours on screen Cac14
HPV brought to set safety position
when alarm from DI activated
Check the device connected to the DI
RPRV brought to set safety position
when alarm from DI activated
Check the device connected to the DI
Compressor shutdown, set on Cae30 Check the correct reading of the probes set for SH (P_suct and T_suct)
Check compressor status (frost on the outside)
Check liquid return from evaporators (SH reading on MPXPRO and UC)
Compressor shutdown Check correct compressor operation (presence of liquid, refrigerant charge, sizing,..)
Check evaporator valve operation and status (valves blocked, incorrect confi guration, wiring,..)
Check MPXPRO/UC setting (probe operation and positioning, correct parameter confi guration, compare probe
reading against pressure gauge reading)
/ Check status of P_GC and T_out_GC probes (type, wiring, correct positioning,..)
Check correct mechanical operation of the fans (wiring, confi guration, sizing in relation to the application,..)
Check HPV valve setting, operation and installation (mechanical operation, sizing in relation to the application,
correct opening/closing)
Check warning threshold setting
/ Check status of P_ric probe (type, wiring, correct positioning,..)
Check RPRV valve setting, operation and installation (mechanical operation, sizing in relation to the application,
correct opening/closing)
Check warning threshold setting
/ Check status of T_out_GC probe (type, wiring, correct positioning,..)
Check mechanical operation of the fans (wiring, confi guration, sizing in relation to the application,..)
Check warning threshold setting
Compressor shutdown, set on Cae42 Check RPRV valve setting, operation and installation (mechanical operation, sizing in relation to the application,
correct opening/closing)
Check synchronisation with external driver (wiring and connections, confi gurations,..)
Sizing of the receiver in relation to the application
Charge in the circuit
Low superheat warning signal
No control action
Check the correct reading of the probes set for SH (P_suct and T_suct)
Check compressor status (frost on the outside)
Check liquid return from evaporators (SH reading on MPXPRO and UC)
Compressor shutdown Check inverter power supply
Check phase connection between compressor and inverter (wiring and connections)
• Check STO
Check confi guration of inverter parameters (baud rate, parity, number of bits)
Compressor shutdown Check inverter operation and status
Check list of alarms in the inverter manual (explanation of the alarms that may occur on the inverter)
Compressor shutdown with manual reset
after n restart attempts
Check compressor connections to the inverter (swapped phases, wiring and incorrect connections,..)
Check correct compressor operation (liquid in the compressor, excessive charge in the circuit,..)
Check evaporator valve status (valves stuck open)
Check positioning, installation and correct operation of P_GC probe (positioning before the check valve at the com-
pressor discharge, checking the values are read correctly)
Check positioning, installation and correct operation of P_suct probe