humiSonic ventilation +0300063EN - rel. 1.3 - 14.05.2021
DIMENSIONS - mm (in)
Fig. 3.f
Note: for UQ18B% dimensions, refer to the quotes indicated in 3.5
section concerning “Main control panel.
POSITIONING
The electrical panel is designed for wall-mounting and features forced
ventilation for cooling. See the fi gure for the minimum clearances in mm
(in) that ensure suffi cient air fl ow and change inside the electrical panel.
<0,5°
Level
≥ 500
(19.7”)
≥ 500
(19.7”)
≥ 500
(19.7”)
≥ 500
(19.7”)
Fig. 3.g
Weight
UQ05B10000 Secondary electrical panel 300 W -110 V 6,5 Kg /14,3 lbs
UQ05BD0000 Secondary electrical panel 300 W -230 V 7 Kg / 15,4 lbs
UQ09B10000 Secondary electrical panel 600 W -110 V 9 Kg / 19,8
UQ09BD0000 Secondary electrical panel 600 W -230 V 7 Kg / 15,4 lbs
UQ18B10000 Secondary electrical panel 1200 W -110 V 11,9 Kg / 26,2 lbs
UQ18BD0000 Secondary electrical panel 1200 W -230 V 11,9 Kg / 26,2 lbs
3.3 “Secondary electrical panel
STRUCTURE
OUTSIDE
1
2
3
4
5
6
Fig. 3.d
INSIDE
10
9
8
7
Fig. 3.e
Key
1 Exhaust air fan 6 Cable glands
2 Cover 7 Light terminal block
3 Air intake 8 Main terminal block
4 ON/OFF switch 9 Transformer
5
LED BLUE power 10 Power supply
RED alarm