33
ENG
“humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021
Mask Display description Notes Def. UOM Min Max Value description Type R/W
Gb01 Information
FLSTDMHUSU SW name
Version 0.3.008B
Date - dd/mm/yy Date software release I R
Bios dd/mm/yy BIOS release date I R
Boot dd/mm/yy BOOT release date I R
Gb02 Information
Board type ---
Board size ---
Total flash 2048 KB I R
RAM 512 KB I R
Built-in type None I R
Main cycle - ms I R
Gb03 Firmw. release - I R
HW Id - I R
Functional Test - I R
c. Working hours
Gc01 Work counter 0 h 0 32767 I R/W
Machine counter 0 h 0 32767 I R/W
Gc02 Hours counter
Maintenance hours 5000 h 0 20000 I R/W
Remainder every 60 min 0 240 I R/W
d. BMS configuration
Service password
Insert service password
(PW1)
Gd01 BMS configuration
Protocol Modbus - Modbus Carel Modbus ¦ Carel D R/W
Speed 19200 bps 1200 19200 1200 ¦ 2400 ¦ 4800 ¦ 9600 ¦ 19200 I R/W
Address 1 - 1 207 I R/W
Gd02 BMS configuration
Serial manager Disabled Disabled On/off +
Control + Limit
Disabled | On/off | On/off + Control |
On/off + Control + Limit
I R/W
e. Service settings
a. Timings
Gea01 Timings
Tmax fill see chapt. 7.7.1 min 0 30 I R/W
Tmax drain see chapt. 7.7.1 s 0 300 I R/W
Empty Drain T. see chapt. 7.7.1 s 0 60 I R/W
Gea02 Timings
Tmax Refill see chapt. 7.7.2 s 1 60 I R/W
Refill time see chapt. 7.7.2 s 0 120 I R/W
Gea03 Timings
Tmax prod. 30 min 1 200 I R/W
Level test at
Tmax production
70 % 50 90
Tmin prod. 1 min 1 200 I R/W
Gea04 Timings
Low lev delay 10 s 0 200 I R/W
Max HLev Time 10 s 1 60 I R/W
Gea05 Timings
Remote board offline time 30 s 0 240 I R/W
Main board offline time 30 s 0 999 I R/W
b. Reset / Default
Geb01 Reset Cnt/Logs
Delete data logger No - No Yes No ¦ Yes D R/W
Reset counter No - No Yes No ¦ Yes D R/W
Geb02 DEFAULT INSTALLATION: erase
user settings and install global
default value (“Main” panel)
No - No Yes No ¦ Yes D R/W
Geb03 Install default parameters on
remote unit
(humidifier)
No - No Yes No ¦ Yes D R/W
c. Access management
Gec01 Access management
Password delay 1 min 0 30 D R/W
Gec02 Access management
Quick menu Yes - No Yes No ¦ Si D R/W
Main menu password No No Yes No ¦ Si D R/W
Gec03 Access management
Insert new main menu
password (PW0)
0000 0000 9999 I R/W
Gec04 Access management
Insert new service password
(PW1)
0000 0000 9999 I R/W
f. Manual management
Gf01 Manual mode
Manual mode No - No Yes No ¦ Yes D R/W
Gf02 Manual management Gf01:mod=si
Fill Off - Off On Off ¦ On D R/W
Drain On - Off On Off ¦ On D R/W
Gf03 Manual management
Mist 1 No - No Yes No ¦ Yes D R/W
Mist 2 No - No Yes No ¦ Yes D R/W
Alarm relè On - Off On Off ¦ On D R/W
Gf04 Manual management
Ambient probe 0 - 0 1000 I R/W
Limit probe 0 - 0 1000
I R/W
Tab. 8.a