8.1 Supervisor variable list
The interface to an RS485 supervisor network using the Carel/Modbus
protocol with a maximum baud rate of 19200 bps requires installation
of the optional opto-isolated card PCOS004850 and the plastic support
PCOS00S030 that fixes the optional card to the electronic control board
slot on the “Main electrical panel board.
The serial line is configured by default with the following parameters:
address 1
baud rate 19200 bps
frame 8, N, 2 (not modifiable)
It is recommended to not set any variables that are not shown in the
table, even if they are visible on the supervisor, so as to not risk comprising
correct humidifier operation.
CAREL Modbus® Analogue variables (Modbus®: REGISTERS) Type Screen index
4 4 Instant production D Main screen
5 5 Main humidifier capacity D i01 (in the absence of Secondaries)
6 6 Secondary humidifier 1 capacity D D02
7 7 Secondary humidifier 2 capacity D D04
8 8 Secondary humidifier 3 capacity D D06
14 14 Preheat set point R/W Fa13
15 15 Preheat differential R/W Fa13
19 19 Total Main + Secondary capacity D i01
20 20 Room probe D Main screen
22 22 Limit probe D Main screen
23 23 Room set point R/W A01
24 24 Limit set point R/W A01
25 25 Min NTC main probe R/W Fa04
26 26 Max NTC main probe R/W Fa04
29 29 Room probe differential R/W Fa07
30 30 Limit probe differential R/W Fa07
31 31 Control hysteresis R/W Fa08
32 32 Maximum value read by active room probe R/W Fa09
33 33 Minimum value read by active room probe R/W Fa09
34 34 Maximum value read by active limit probe R/W Fa09
35 35 Minimum value read by active limit probe R/W Fa09
Tab. 8.b
CAREL Modbus® Digital variables (Modbus®: COILS) Type Screen index
9 9 Low level R i03
10 10 High level R i03
12 12 Autotest completed R -
18 18 Production in progress R -
19 19 Fill R -
20 20 Drain R -
21 21 Piezoelectric transducers row 1 status R -
22 22 Piezoelectric transducers row 2 status R -
26 26 Manual drain R/W Gf02
28 28 Reset counter R/W Geb01
29 29 Reset alarms R/W -
34 34 Secondary 1 online R D01
35 35 Secondary 2 online R D01
36 36 Secondary 3 online R D01
39 39 Skipping wash R/W -
40 40 Disable Secondary 1 R/W -
41 41 Disable Secondary 2 R/W -
42 42 Disable Secondary 3 R/W -
50 50 Manual mode R/W Gf01
51 51 Alarm relay R -
52 52 Status relay R -
53 53 Remote on/off R -
54 54 Humidistat status R -
55 55 On/Off from keypad R/W A01
57 57 Enable scheduler R/W C03
58 58 Unit of measure SI/IP R/W Fa01
59 59 Analogue room probe/HYHU R/W Fa03
60 60 Digital humidistat input logic R/W Fa10
61 61 Enable manual wash activation from screen A01 R/W Fb02
62 62 Enable manual wash activation from BMS serial R/W Fb02
63 63 Serial wash command R/W -
64 64 Enable wash during operation R/W Fb03
65 65 Unit of measure for wash time during operation R/W Fb03
66 66 Enable wash due to inactivity R/W Fb04
67 67 Unit of measure for wash time due to inactivity R/W Fb04
68 68 Unit of measure for total wash time R/W Fb05
69 69 Enable day selection for programmed washing R/W Fb06
70 70 Type of digital input for physical washing event R/W Fb07
71 71 Digital input logic for physical washing event R/W Fb07
72 72 Request logic for physical washing event R/W Fb08
73 73 Washing only if ready R/W Fb09
74 74 Alarm relay logic R/W Fc02
75 75 Status relay function R Fc02
76 76 State relay logic R/W Fc02
78 78 Disable via serial R/W -
82 82 Enable preheat probe R/W Fa12
Tab. 8.c