22
ENG
“UEX-PLUS” +03U0040EN - Rel. 1.35 - 10.05.2013
installeruserservice
OFF by Keyb.: steam production disabled by keyboard (see “SET
mask);
Manual Proc.: humidi er functions managed manually (maintenance
menu > manual procedure);
No request: humidi er on, without steam production request.
Hour counter display UOM
Total hours
value h
Cylinder 1
Operating hours
value h
Cylinder 2
Operating hours
value h
Time bands active
YES/NO
Current
Info cylinder 1 display UOM
Cyl. prod.
value lbs/h
Status
(*)
Activity
cylinder activity (**)
Current
value A
Power contactor
YES/NO
Fill valve
YES/NO
Drain pump
YES/NO
Info cylinder 2 display UOM
Cyl. prod.
value lbs/h
Status
(*)
Activity
activity of the cylinder (**)
Current
value A
Power contactor
YES/NO
Fill valve
YES/NO
Drain pump
YES/NO
(*) cylinder status:
Off: stop steam production (no request or signaling of an alarm)
Softstart: starting steam production;
Operating: steady operation steam production;
Low Prod.: low production;
Washing: cylinder washing in progress.
(**) Activity of the cylinder:
Cyl.Off: stop steam production (no request or signaling of an alarm);
Fill:  ll valve operating;
Evaporation: steam production operating;
Drain: drain pump operating;
Stop by Al.: steam production stopped by an alarm;
Inact.Drain: total drain for inactivity;
Pre-clean: new cylinder washing in progress;
M. Emptying: manual drain;
Chk.F.Water:  ll water check (from lack of water cylinder alarm);
Period FI: Periodical drain for dilution.
6.7 SET” mask
Used to set the main values for the humidi er.
To access, press ENTER from the “Main screen, to move from one value to the
next press UP (next) or DOWN (previous) and ENTER to con rm.
Press ESC repeatedly to return to the “Main screen.
Parameter range default UOM
Set point 0 to 100
50 %rH
Humidifi er AUTO / OFF
AUTO
Max. prod. 20 to 100
100 %
Prop. band. 2 to 19.9
5 %rH
Lim. probe set * 0 to 100
80 %rH
Prop. band * 2 to 19.9
5 %rH
* visible only if the limit probe is enabled
Manual drain:
access the “SET screen,
press UP and DOWN together for 5 seconds
The same procedure can be repeated to stop the drain cycle