35 163 R/W system timer: month (can be edited for updating the sistem timer!)
36 164 R/W system timer: year (can be edited for updating the sistem timer!)
37 165 R cylinder 1: hour counter
38 166 R cylinder 2: hour counter
39167 R voltage type (v):
0 = 200; 1 = 208; 2 = 230; 3 = 400; 4 = 460; 5 = 575
40 168 R/W humidi er type
52 180 R lista modelli umidi catori
53 181 R/W parameter Installer/Supervisor/Supervisor connect/Reg. from BMS: sending analog signal control(0-1000, temper:
tenths of °C/°F, umid: tenths of rH%)
54182 R/W parameter Installer/Supervisor/Supervisor connect/O ine al. D elay: time delay for alarm SERIAL OFFLINE (seconds)