Fig.5.p
Ref. Description
t Time
dt1 End defrost temperature
dP1 Maximum defrost duration
Ref. Description
Sd Defrost probe
DEF Defrost
The heater defrost by time with temperature control (d0=4) activates the defrost output only if the
evaporator temperature (Sd) is less than the value of parameter dt1, and ends after the time defined by
dP1. This function is useful for energy saving and to prevent excessive temperatures on the evaporator.
5.3.1 Heater defrost (d0 = 0, 2, 4): duty cycle
The duty cycle refers to the default values of parameters F2 and F3. The electronic valve can be opened
to the initial value set for cP1 for a period equal to Pdd.
Fig.5.q
Ref. Description
t Time
FAN Fan
DEF Defrost
drip Dripping
Ref. Description
SV/CMP Solenoid/compressor
EEV Electronic expansion valve
Pdd Valve position maintenance time after defrost
Post drip Post-dripping
Fig.5.r
The pump down phase is the period in which the evaporator is emptied of liquid refrigerant, and can be
disabled by setting dH1=0 (see the paragraph "Pump down phase duration"). Operation of the fan
62|5. Functions