EasyManua.ls Logo

Carrier 160 Series - Page 39

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
b.
When
thermometer
readings
stabilize,
subtract
return-
air
temperature
from
supply-air
temperature
to
determ-
ine
air
temperature
rise.
NOTE:
Temperature
rise
can
be
determined
for
low-heat
operation
by
placing
setup
switch
SW1-2
on
furnace
control
in
ON
position.
For
high-heat
operation,
place setup
switch
SW1-2
in
OFF
position
and
jumper
R-W2
on
furnace
control.
DO
NOT
forget
to
return
setup
switch
to
OFF
position
and
remove
R-W2
jumper
upon
completion
of
testing.
c.
This
furnace
is
capable
of
automatically
providing
proper
airflow
to
maintain
the
temperature
rise
within
the
range
specified
on
furnace
rating
plate.
If
temperat-
ure
rise
is
outside
this
range,
proceed
as
follows:
(1.)
Check
gas
input
for
low-
and
high-heat
opera-
tion.
(2.)
Check
derate
for
altitude
if
applicable.
(3.)
Check
all
return
and
supply
ducts
for
excessive
restrictions
causing
static
pressure
greater
than
0.5-In.
W.C..
(4.)
Ensure
Low
Heat
Rise
Adjust
switch
SW1-3
on
furnace
control
is
in
ON
position
when
a
bypass
humidifier
is
used.
(See
Fig.
26
for
switch
loca-
tion.)
(5.)
Make
sure
proper
model
plug
is
installed.
d.
Remove
thermostat
jumpers
and
release
blower
access
door
switch.
e.
Repeat
Steps
a
through
c
as
required
to
adjust
for
high
heat
temperature
rise.
f.
When
correct
high
heat
input
rate
and
temperature
rise
is
achieved,
turn
gas
valve
ON/OFF
switch
to
OFF.
g.
Release
blower
access
door
switch.
h.
Remove
manometer
or
similar
device
from
gas
valve.
i.
Re-install
manifold
pressure
tap
plug
in
gas
valve.
(See
Fig.
49.)
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Reinstall
manifold
pressure
tap
plug
in
gas
valve
to
prevent
gas
leak.
j.
Remove
thermostat
jumper
wire
from
furnace
control
board.
k.
Turn
gas
valve
ON/OFF
switch
to
ON.
FURNACE
OVERHEATING
HAZARD
Failure
to
follow
this
caution
may
result
in
reduced
furnace
life.
Recheck
temperature
rise.
It
must
be
within
limits
specified
on
the
rating
plate.
Recommended
operation
is
at
the
mid-point
of
rise
range
or
slightly
above.
1.
Proceed
to
Step
6,
“Set
Blower
Off
Delay”
before
in-
stalling
blower
access
door.
7,
Set
Blower
Off
Delay
a.
Remove
blower
access
door
if
installed.
b.
Turn
Dip
switch
SW-7
or
SW-8
ON
or
OFF
for
de-
sired
blower
off
delay.
(See
Table
10
and
Fig.
26
and
53.)
8.
Set
thermostat
heat
anticipator.
a.
Mechanical
thermostat.
Set
thermostat
heat
anticipator
to
match
the
amp.
draw
of
the
electrical
components
in
the
R-W/W1
circuit.
Accurate
amp.
draw
readings
can
be
obtained
at
the
wires
normally
connected
to
ther-
mostat
subbase
terminalis,
R
and
W.
The
thermostat
anticipator
should
NOT
be
in
the
circuit
while
measur-
ing
current.
(1.)
Set
SW1-2
switch
on
furnace
control
board
to
ON.
(2.)
Remove
thermostat
from
subbase
or
from
wall.
(3.)
Connect
an
amp.
meter
as
shown
in
Fig.
51.
across
the
R
and
W
subbase
terminals
or
R
and
W
wires
at
wall.
(4.)
Record
amp.
draw
across
terminals
when
furnace
is
in
low
heat
and
after
blower
starts.
(5.)
Set
heat
anticipator
on
thermostat
per
thermostat
instructions
and
install
on
subbase
or
wall.
(6.)
Turn
SW1-2
switch
OFF.
(7.)
Install
blower
access
door.
b.
Electronic
thermostat:
Set
cycle
rate
for
3
cycles
per
hr.
9,
Set
Airflow
for
Air
Conditioning
-Single
Stage
and
High
Stage
Cooling
The
ECM
blower
can
be
adjusted
for
a
range
of
airflow
for
Low
Speed
or
High
Speed
cooling.
See
Table
5-Air
Delivery
-
CFM
(With
Filter
),
Depending
on
the
model
size,
the
cooling
airflow
can
be
adjusted
from
1.
tons
nom-
inal
cooling
to
3
.,
to
4
or
to
6
tons
of
nominal
cooling
based
on
350
cfm
ton.
The
cooling
airflow
is
adjusted
by
turning
Setup
switches
SW2-1,
SW2-2
and
SW2-3
either
ON
or
OFF.
Select
the
required
airflow
from
Fig.
57.
Fig.
57
is
based
on
350
CFM
per
ton.
For
airflow
at
400
CFM
per
ton,
turn
Setup
SW1-5
ON
(See
Table
10
and
Fig.
26
and
53.)
NOTE:
6
ton
airflow
will
truncate
at
2200
cfm
on
applicable
models.
For
a
complete
explanation
of
cooling
airflow,
refer
to
the
section
titled
“Sequence
of
Operation.”
10.
Set
Airflow
For
Continuous
Fan/Low
Speed
Cooling
Air-
flow
The
ECM
blower
motor
can
be
adjusted
for
continu-
ous
fan
speeds
different
than
heating
or
cooling
fan
speed.
See
Table
5
-
Air
Delivery
-
CFM
(With
Filter).
Select
the
required
continuous
fan
airflow
from
Fig.
57.
The
continuous
fan
speed
is
also
the
fan
speed
for
low
speed
cooling
when
furnace
is
used
with
a
2-speed
cool-
ing
unit.
Adjust
the
Continuous
Fan
CFM
to
match
the
airflow
required
for
low
speed
cooling.
Select
the
required
airflow
from
Fig.
55.
For
airflow
at
400
CFM
per
ton,
turn
Setup
SW1-5
ON
(See
Fig.
57.)
The
airflow
selected
for
low
speed
cooling
will
also
be
the
airflow
used
for
con-
tinuous
fan.
The
continuous
fan
speed
can
be
further
adjusted
at
the
thermostat
using
the
“Comfort
Fan”
select
function.
Changing
the
continuous
fan
speed
at
the
thermostat
DOES
NOT
change
the
low
speed
cooling
airflow
selec-
ted
at
the
control
board.
58CV

Related product manuals