LEGEND
CB Circuit Breaker
COMM Communications
N.C. Normally Closed
N.O. Normally Open
O.L. Overload
PR Pilot Relay
PWR Power
RLA Rated Load Amps
SMM Starter Management Module
TB Terminal Board
TEWAC Totally-Enclosed Water-To-Air Cooled
Starter Vendor Supplied Wiring
Field Wiring
Carrier Factory Wiring
NOTE: Voltage to terminals LL1 and LL2 comes from a control trans-
former in a starter built to Carrier specifications. Do not connect an
outside source of control power to the compressor motor starter (ter-
minals LL1 and LL2). An outside power source will produce danger-
ous voltage at the line side of the starter, because supplying voltage
at the transformer secondary terminals produces input level voltage
at the transformer primary terminals.
Fig. 59 Elementary Wiring Diagram for Starter Management Module (SMM) and Control Interface
Between Starter and Machine Power Panel (For Low and Medium Free-Standing Starters)
CONT’D