Enable Excessive Starts
No
*
Oil Stir Cycle (19XR6/7)
No Stir = 0, 30s/30m = 1, 1m/4h = 2, Comb.
0&1=3
1
*
* : Most Service Parameters do not require any change from default. Adjust as required.
TABLE
SETPOINT
Access Menu
Main Menu / Setpoint
Setting
Default value (SI units)
Settings value (SI)
Cooling ECW Setpoint
12
job site specific
Cooling LCW Setpoint
7
job site specific
Heating ECDW Setpoint
40
job site specific
Heating LCDW Setpoint
45
job site specific
Ice Build setpoint
4.4
job site specific
Base Demand limit
100%
100%
EWT Control Option
Disable
job site specific
TABLE
CONF_IOB - IOB configuration
Access Menu
Configuration Menu / IOB Configuration
Setting
Default value
Settings value
IOB1 AI#1 Type
4
4
Entering chilled water temperature
IOB1 AI#2 Type
4
4
Leaving chilled water temperature
IOB1 AI#3 Type
4
4
Entering condenser water temperature
IOB1 AI#4 Type
4
4
Leaving condenser water temperature
IOB1 AI#9 Type
2
0
nothing
IOB1 AO#1 Type
1
1
Chiller status output mA
IOB2 AI#1 Type
4
4
Motor winding temperature 1
IOB2 AI#2 Type
4
0
IOB2 AI#3 Type
4
2
EC option
IOB2 AI#4 Type
0
0
IOB2 AI#8 Type
0
2
Auto Demand limit input
IOB2 AI#9 Type
0
0
No Refrigerant leak sensor
IOB2 AI#10 Type
5
1
IOB2 AO#1 Type
1
1
Guide Vane1 output
IOB2 AO#2 Type
1
0
not used
IOB3 AI#1 Type
4
4
1st stage bearing temp
IOB3 AI#2 Type
4
4
2nd stage bearing temp
IOB3 AI#3 Type
4
4
Bearing ref supply temp
IOB3 AI#4 Type
4
2
Guide Vane 2 actual position
IOB3 AI#5 Type
0
4
Remote Reset Sensor
IOB3 AI#6 Type
5
2
Guide Vane 1 Actual Pos
IOB3 AI#8 Type
0
0
Auto Water Temp Reset
IOB3 AI#9 Type
0
0
Common CHWR Temp, not used
IOB3 AI#10 Type
0
0
not used
IOB3 AO#1 Type
1
1
Head Pressure Output
IOB3 AO#2 Type
1
0
not used
IOB4 AI#3 Type
0
1
Entering Evap water pressure
IOB4 AI#4 Type
0
1
Leaving Evap water pressure
IOB4 AI#5 Type
0
1
Entering Cond water pressure
IOB4 AI#6 Type
0
1
Leaving Cond water pressure
IOB4 AI#7 Type
0
0
not used
IOB4 AI#10 Type
0
0
not used
ISM Input Enable
Disable
Disable
Information for IOB input (AI) type as below:
0 : not used
1 : 0 5V
2 : 0 20 mA
3 : 10 K