Table 2 LID Screens (cont)
EXAMPLE2—STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
DESCRIPTION
POINT TYPE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
INPUT OUTPUT
Hot Gas Bypass Relay X OFF/ON HGBR
*Chilled Water Pump X OFF/ON CHWP
Chilled Water Flow X NO/YES EVFL
*Condenser Water Pump X OFF/ON CDP
Condenser Water Flow X NO/YES CDFL
Compressor Start Relay X OFF/ON CMPR
Compressor Start Contact X OPEN/CLOSED 1CR AUX
Compressor Run Contact X OPEN/CLOSED RUN AUX
Starter Fault Contact X OPEN/CLOSED STR FLT
Pressure Trip Contact X OPEN/CLOSED PRS TRIP
Single Cycle Dropout X NORMAL/ALARM V1 CYCLE
Oil Pump Relay X OFF/ON OILR
Oil Heater Relay X OFF/ON OILH
Motor Cooling Relay X OFF/ON MTRC
*Tower Fan Relay X OFF/ON TFR
Compr. Shunt Trip Relay X OFF/ON TRIPR
Alarm Relay X NORMAL/ALARM ALM
Spare Prot Limit Input X ALARM/NORMAL SPR PL
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations from the LID only.
EXAMPLE3—STATUS03 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS03.
4. Press SELECT
.
DESCRIPTION RANGE UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
OPTIONS BOARD 1
*Demand Limit 4-20 mA 4-20 mA DEM OPT
*Temp Reset 4-20 mA 4-20 mA RES OPT
*Common CHWS Sensor –40-245 (–40-118) DEG F (DEG C) CHWS
*Common CHWR Sensor –40-245 (–40-118) DEG F (DEG C) CHWR
*Remote Reset Sensor –40-245 (–40-118) DEG F (DEG C) R RESET
*Temp Sensor Spare 1 –40-245 (–40-118) DEG F (DEG C) SPARE1
*Temp Sensor Spare 2 –40-245 (–40-118) DEG F (DEG C) SPARE2
*Temp Sensor Spare 3 –40-245 (–40-118) DEG F (DEG C) SPARE3
OPTIONS BOARD 2
*4-20 mA Spare 1 4-20 mA SPARE1 M
*4-20 mA Spare 2 4-20 mA SPARE2 M
*Temp Sensor Spare 4 –40-245 (–40-118) DEG F (DEG C) SPARE4
*Temp Sensor Spare 5 –40-245 (–40-118) DEG F (DEG C) SPARE5
*Temp Sensor Spare 6 –40-245 (–40-118) DEG F (DEG C) SPARE6
*Temp Sensor Spare 7 –40-245 (–40-118) DEG F (DEG C) SPARE7
*Temp Sensor Spare 8 –40-245 (–40-118) DEG F (DEG C) SPARE8
*Temp Sensor Spare 9 –40-245 (–40-118) DEG F (DEG C) SPARE9
NOTE: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*) support write operations for BEST
programming language, data transfer, and overriding.
EXAMPLE 4 SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SETPOINT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Base Demand Limit 40-100 % DLM 100
LCW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) lcw sp
50.0 (10.0)
ECW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) ecw sp
60.0 (15.6)
ICE BUILD Setpoint 20- 60 (–6.7-15.6) DEG F (DEG C) ice sp 40.0 ( 4.4)
22