10/11
Resettable
Fault
10024
11024
Phase
WNegToGrnd
Phase W Negative To Ground. A phase
to ground fault has been detected
between the drive and motor in this
phase.
Rotate U/T1, V/T2, W/T3 connections.
If the problem follows the wire, suspect
a field wiring problem. If no change,
suspect a problem with the drive.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10028
11028
Drive OverLoad
Drive OverLoad. Parameter 10:357 [Drive
OL Count] has exceeded 100%. Possible
causes include loads that require too
much current and power, improper
derating for temperature and altitude, and
obstructed airflow.
Verify that the drive is sized and
derated correctly. Check the condition
of cabinet air filters.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 3 ‘MS Pwr Flts’.
10/11
Resettable
Fault
10029
11029
Stator Res Range
Stator Resistance Range. Parameter
10:910 [Autotune] is set to 2 ‘Static MtrID’
or 3 ‘Rotate MtrID’ and the value for stator
resistance in parameter 10:512 [u IM
Stator Res] measured by the Autotune
function is not in the range of acceptable
values.
Verify that the correct motor nameplate
data is entered.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10030
11030
FluxAmpsRef Rang
Flux Amps Reference Range. Parameter
10:910 [Autotune] is set to 2 ‘Static MtrID’
or 3 ‘Rotate MtrID’ and the value for flux
amps in parameter 10:518 [u Flux Cur
Ref] measured by the Autotune function
exceeds the value that is programmed in
parameter 10:401 [Motor NP Amps].
Verify that the correct motor nameplate
data is entered.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10031
11031
Excessive Load
Excessive Load. The motor did not come
up to speed in the allotted time during
Autotune.
Decrease load on the motor. Uncouple
motor. For induction motors, run a
static MotorID test. For systems with
encoders, perform a Direction test first.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10032
11032
AutoTune Aborted
Autotune Aborted. The Autotune function
was interrupted. This interruption was the
result of manual cancellation or a fault.
If not intended, ensure no stop signal is
issued during an autotune. See
parameter 0:604 [M Last Stop Src].
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10033
11033
Leakage L Range
Leakage Inductance Range. Parameter
10:910 [Autotune] is set to 2 ‘Static MtrID’
or 3 ‘Rotate MtrID’ and the voltage that
was measured for motor inductive
impedance exceeds 25% of the value of
parameter 10:400 [Motor NP Volts].
Verify that the correct motor nameplate
data is entered.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10034
11034
StcOffstPulsFail
PM Static Offset Pulse Test Failure. PM
Pulse Test failed due to IOC overcurrent
or pulse test time determined was larger
than the maximum allowed pulse test
time.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 8 ‘Fdbk Faults’.
10/11
Resettable
Fault
10035
11035
StcOffstRtrFail
PM Static Offset Rotor Test Failure. PM
Rotor position not found during the static
offset test.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: Yes. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 2 ‘MS Ctrl Flts’.
10/11
Resettable
Fault
10038
11038
Auto Tach Switch
Auto Tach Switch. Both the primary
feedback and alternate feedback devices
have failed.
Investigate feedback device failure.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: 0:455 [Emerg Prot
OVRD] bit 8 ‘Fdbk Faults’.
10/11
Resettable
Fault
10042
11042
PrechargeOpenFlt
Precharge Open Fault. The internal
precharge-circuity-bypass relay (for
drives) or main contactor (for CBIs) was
commanded to open while the drive was
running (PWM was active) due to low DC
bus voltage. The internal fault latch is
automatically cleared when PWM is
disabled.
Investigate low DC bus voltage or the
reason the drive entered precharge.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10043
11043
Autn Enc Angle
Autotune Encoder Angle. The autotune
failed to calculate Parameter 10:521 [u
EncLs AngCmp] within range. This can
only occur for encoderlesss systems in
Induction Flux Vector mode.
Verify motor nameplate data and cable
length to the motor are correct. See
publication DRIVES-IN001.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: Cannot override
this fault.
10/11
Resettable
Fault
10044
11044
Autn Vel Rstrct
Autotune Velocity Restricted. Velocity
Command is too low (< 25% base speed)
to complete the inertia test. This condition
is applicable to induction and permanent
magnet motors.
Configure the drive to be allowed to
reach at least 25% base speed.
Coast (Motor Side Inverter).
Additional Fault Action. Fault opens
main circuit breaker: No. Fault can
automatically reset: No. Emergency
override response: N/A
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE