24
DETAI LED COOLING CAPACITIES
#
CONTINUED
Evaporator Air
CONDENSER ENTERING AIR TEMPERATURES _F(_C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
Capacity MBtuh†
Total
System
KW**
Capacity MBtuh†
Total
System
KW**
Capacity MBtuh†
Total
System
KW**
Capacity MBtuh†
Total
System
KW**
Capacity MBtuh†
Total
System
KW**
Capacity MBtuh†
Total
System
KW**
Total Sens‡ To t al Sens‡ Total Sens‡ Total Sens‡ To tal Sens‡ Total Sens‡
25HBA360A31 Outdoor Section With FY4ANF060 Indoor Section
1750
72 71.08 36.09 4.41 67.69 34.77 4.86 64.09 33.39 5.36 60.33 31.96 5.90 56.30 30.45 6.50 51.84 28.81 7.14
67 65.19 45.05 4.36 62.05 43.69 4.81 58.73 42.27 5.30 55.30 40.82 5.85 51.61 39.29 6.44 47.57 37.62 7.09
63
{{
60.79 43.67 4.31 57.85 42.31 4.76 54.78 40.90 5.26 51.57 39.45 5.81 48.15 37.91 6.40 44.41 36.26 7.05
62 59.61 53.90 4.30 56.75 52.49 4.75 53.77 51.00 5.25 50.69 49.41 5.80 47.50 47.50 6.40 45.90 45.90 6.36
57 57.48 57.48 4.28 55.20 55.20 4.74 52.79 52.79 5.24 50.24 50.24 5.79 47.49 47.49 6.40 44.42 44.42 7.06
2000
72 72.12 37.62 4.54 68.55 36.26 4.99 64.87 34.89 5.48 60.98 33.44 6.03 56.80 31.91 6.62 52.19 30.25 7.26
67 66.24 47.72 4.48 62.96 46.34 4.93 59.50 44.89 5.43 55.93 43.42 5.97 52.11 41.85 6.57 47.93 40.14 7.21
63
{{
61.83 46.19 4.44 58.77 44.80 4.89 55.56 43.36 5.38 52.22 41.88 5.93 48.67 40.31 6.53 44.80 38.60 7.18
62 60.73 57.58 4.43 57.79 56.05 4.88 54.77 54.33 5.38 51.88 51.88 5.93 48.94 48.94 6.53 47.37 47.37 6.51
57 59.63 59.63 4.42 57.18 57.18 4.87 54.60 54.60 5.38 51.89 51.89 5.93 48.94 48.94 6.53 45.66 45.66 7.19
2250
72 72.83 39.05 4.66 69.16 37.69 5.11 65.40 36.31 5.61 61.39 34.85 6.15 57.10 33.30 6.74 52.35 31.61 7.37
67 66.96 50.26 4.61 63.58 48.86 5.06 60.01 47.39 5.55 56.35 45.89 6.09 52.43 44.28 6.69 48.14 42.52 7.33
63
{{
62.58 48.57 4.56 59.40 47.16 5.01 56.09 45.69 5.51 52.66 44.18 6.05 49.01 42.56 6.65 45.05 40.80 7.30
62 61.68 60.83 4.56 58.79 58.79 5.01 56.05 56.05 5.51 53.19 53.19 6.06 50.08 50.08 6.66 46.62 46.62 7.31
57 61.37 61.37 4.55 58.79 58.79 5.01 56.06 56.06 5.51 53.19 53.19 6.06 50.08 50.08 6.66 46.62 46.62 7.31
Cooling Indoor Model Capacity Power Furnace Model
*FY4ANB060 1.00 1.00
FV4BNB006 1.01 0.95
FX4CN(B,F)060 1.01 0.91
CAP**6021A** 0.99 0.99
CAP**6024A** 1.01 1.01
CNPH*6024A** 1.00 1.00
CNPV*6024A** 1.00 1.00
CSPH*6012A** 1.01 1.01
CAP**6021A** 0.97 0.94 58CV(A,X)110--- 20
CNPH*6024A** 0.98 0.95 58CV(A,X)110--- 20
CSPH*6012A** 0.99 0.96 58CV(A,X)110--- 20
CAP**6024A** 0.99 0.93 58CV(A,X)135--- 22
CNPH*6024A** 0.98 0.95 58CV(A,X)135--- 22
CNPV*6024A** 0.98 0.95 58CV(A,X)135--- 22
CSPH*6012A** 0.99 0.93 58CV(A,X)135--- 22
CAP**6024A** 0.99 0.93 58CV(A,X)155--- 22
CNPH*6024A** 0.99 0.93 58CV(A,X)155--- 22
CNPV*6024A** 0.99 0.93 58CV(A,X)155--- 22
CSPH*6012A** 0.99 0.93 58CV(A,X)155--- 22
* Tested combination.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor un it at the same elevation per ARI standard 210/240---94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB Entering Wet Bulb
25HBA3