There is an LED on the GMC board that displays any
board errors.
The error code can be identied from the ashing LED
using the following table. In the case of more than one
error, the error with the highest priority will be displayed
until it is resolved.
In the case of normal operation, the LED ashes at a
frequency of ½ Hz. In the case of an error, the LED
remains of for 4 seconds, then at a frequency of 1Hz, it
ashes a number of times equal to the error code and then
remains off again for 6 seconds. If the error code has 2
digits, the ashing is interrupted for 2 seconds between the
rst and second digits.
Example: Error 23: LED of for 4 seconds. 2 ashes at a
frequency of 1Hz. Off for 2 seconds. 3 ashes at a
frequency of 1Hz. Off for 6 seconds. The cycle repeats until
the LED turns off because the problem is resolved or if an
error with higher priority occurs.
Frozen plates exchanger
If this fault code is displayed, it means that the plates
exchanger froze during cooling operation.
The only way to restart the unit is to powered OFF -->ON
the unit.
Before doing this operation, contact the qualied service.
The full installation conguration must be checked (unit
and water loop).
Fault Code Description
2 Safety Input
3 Frozen plates exchanger
4 Actual Refrigerant Temperature Sensor (TR)
5 Outdoor Air Sensor of GMC
6 Loss communication to NUI control
7 NUI control Room Sensor
9 Flow Switch error / Water Pump
10 EEProm Corrupt
11 User interface setting mismatch
12 4 Way valve error
13 Loss Communication to RS485 (system coniguration type 6)
14 Loss of Signal From inverter board or High Temperature Release
15 Exit water Temperature Sensor (LWT)
16 Alarm Test
17 Inverter Air Sensor (TO)
18 G-Tr inverter short circuit protection
20 Compressor position Detection Circuit error
21 Inverter Current Sensor error
22 Heat Exchanger Sensors (TE) / (TS)
23 Discharge Temperature Sensor (TD)
24 Outdoor Fan motor error
26 Other unit error
27 Compressor Lock
28 Discharge Temperature error
29 Compressor Breakdown
30 Low pressure system error
31 High pressure system error

Type of safety device Switch on pressure Release
Pressure switch on water 300kPa N.A.
Anti-Freeze Protection Adjustable from 3 to 9 °C software controlled
Delayed compressor start
OFF-->ON
180 s max*
Delayed compressor stop
ON-->OFF
180 s*
Start Acceleration Limit
compressor
6 accelerations/h*
* 6 acceleration/h logic has the priority
IMPORTANT: During functioning in heat pump heating
mode, the unit performs defrost cycles to eliminate any
ice that might form at low temperatures inside the
outdoor unit.

Cleaning the coil
If necessary, proceed as follows for more careful cleaning
of the coil:
Switch the mains supply OFF.
Remove unit top cover by loosening the xing screws and
lifting the cover. Carefully clean the coil with a vacuum
cleaner from inside to outside. With the same vacuum
cleaner, remove the dust from inside the fan compartment
and the fan blades. Avoid any damage to the blades which
may cause future vibrations and noise.
Replace the unit cover and tighten the screws.
IMPORTANT: The operation must be performed by
qualied personnel.
11.1 - Refrigerant charge check
This check becomes necessary after any refrigerant leak or
after replacement of the compressor.
The best method to correctly charge refrigerant is to
completely empty the refrigerant circuit using refrigerant
recovery equipment.
Then charge the exact quantity of refrigerant according to
the data shown on the unit nameplate. R-410A systems
must be charged with liquid refrigerant. Use the special
recharging equipment (normally in the market) to handle
the refrigerant correctly. The oil used for the compressor is
ESTER OIL VG74 (VG68 for size 12kW).
Do not use refrigerants and lubricant besides those
specied. Do not compress air (there must be no air
intake due to leakage in the refrigeration cycles).