Carrier 30HL - Unit Safety Device Checks; Capacity Control System Operation

Carrier 30HL
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check
Unit
Safety
Devices
SAFETY
THERMOSTAT
(Fig.
6)
The
low
water
temperature
cutout
(LWTC)
pro¬
tects
the
unit
against
freeze-up
due
to
operating
mal¬
function.
The
sensing
bulb
is
inserted
into
a
well
located
in
the
leaving
water
nozzle.
As
installed,
the
standard
control
is
factory
set
to
open
at
36
±
2
F,
breaking
the
control
circuit
and
locking
out
unit.
The
contacts
remake
at
5
±
2
F
above
cutout
point,
but
the
control
circuit
switch
must
be
pressed
to
OFF
and
then
to
ON
for
unit
restart.
This
action
re¬
energizes
the
control
circuit
and
starts
the
timer
under
Time
Guard®
control.
The
thermostat
cuts
out
in
a
range
down
to
-30
F,
but
to
obtain
this
range,
the
low-limit
stop
tab
on
the
underside
of
dial
must
be
either
cut
or
bent.
Make
this
adjustment
only
if
necessary
(when
cooling
glycols
or
brines).
HIGH-PRESSURE
SWITCH
(HPS)
The
HPS
settings
are
nonadjustable.
Table
6
shows
factory
settings
for
this
switch.
If
HPS
cuts
out
while
unit
is
in
normal
operation
(2-1/2
minutes
or
more
after
compressor
start-up),
compressor
will
stop
and
lock
out.
To
restart
com¬
pressor,
the
ON-OFF
control
circuit
switch
must
be
manually
pressed
to
OFF
and
then
to
ON.
The
timer
will
start,
and
after
approximately
5-1/2
min¬
utes,
the
compressor
will
start
under
Time
Guard
control.
If
the
pressure
has
not
dropped
to
the
HPS
cut-in
point
(see
Table
6),
the
compressor
will
stop
again
immediately
and
again
lock
out.
Do
not
attempt
to
restart
until
trouble
is
found
and
corrected.
Unless
control
circuit
switch
is
pressed
to
OFF
at
this
time,
timer
will
continue
to
run.
Table
6 —
Pressure
Switch
Specifications
UNIT
30
1
HK
i
HL
PRESSURE
RANGE
(psig)
1
High
1
1
Low
1
Fixed
*
Fixed
10
to
90
Adjustable
DIFFERENTIAL
SETTING
(psi)
High
1
Low
1
96
±
17
(Fixed)
|
1
03
±
1
9
(Fixed)
i
13
to
50
Adjustable
Cutout
Cut-in
1
Cutout
Cut-in
FACTORY
SETTING
(psig)
1
High
1
Low
260
±10
29
±
4
335
±
10
44
±
41
29
±
4
44
±
4
LOW-PRESSURE
SWITCH
(EPS)
The
EPS
is
bypassed
for
2-1/2
minutes
after
compressor
start
on
all
start-ups.
The
EPS
has
an
adjustable
range
from
10
to
90
psig
and
a
differential
of
13
to
50
psi.
See
Fig.
7.
Table
6
shows
factory
settings
for
this
switch.
If
EPS
cuts
out
while
unit
is
in
normal
operation
(any
time
after
2-1/2
minutes
from
compressor
start-up)
timer
starts
and
runs
for
approximately
5-1/2
minutes.
The
compressor
then
starts,
by¬
passing
the
EPS
for
2-1/2
minutes
under
Time
Guard
control.
If
the
EPS
cut-in
pressure
is
reached
within
2-1/2
minutes,
compressor
continues
to
run;
if,
on
the
other
hand,
the
required
pressure
has
not
built
up,
compressor
stops
at
end
of
2-1/2
minutes
and
locks
out.
Do
not
attempt
to
restart
unit
until
trouble
has
been
found
and
corrected.
The
LPS
contacts
must
he
closed
bejore
compressor
can
he
restarted
after
lockout.
/
RANGE
ADJ
SCREW
TURN
CLOCKWISE
TO
RAISE
BOTH
CUT-IN
AND
CUTOUT
(7
PSI
PER
TURN)
DIFFERENTIAL
ADJ
SCREW
TURN
clockwise
TO
DECREASE
(8
PSi
PER
TURN).
ONLY
CUTOUT
CHANGES
(RIGHT
SIDE
OF
CONTROL
BOX,
VIEWED
FROM
TOP)
Fig.
7
Low-Pressure
Switch
(LPS)
Adjustment
Check
Capacity
Control
System
DESCRIPTION
Capacity
control
is
a
system
which
loads
and
unloads
compressor
cylinders
and
starts
and
stops
compressor
to
maintain
load
requirements.
System
includes
a
3-step
temperature
controller
and
cyl¬
inder
unloaders
(see
Table
2).
Table
7
shows
ca¬
pacity
control
steps.
Table
7
Capacity
Control
Steps
UNIT
30HK.
30HL
1
CONTROL
1
!
%
1
OPER
STEPS
CAP.
1
CYL
L....
.
1
1
33
t
.
2
015
I
2
67
4
3
_
1
i
100
6
1
1
35
2*
020
I
2
so
2
I
3
1
100
4
025.
I
1
2
i
33
67
2
4
030
3
1
100
i
6
*Uses
hot
gas
bypass.
3-STEP
TEMPERATURE
CONTROLLER
This
controller
consists
of
3
load
switches
actu¬
ated
by
pressures
developed
in
a
temperature¬
sensing
bulb
located
in
return
water
line
of
chilled
water
system.
The
controller
is
factory
set
to
control
from
return
water
temperature
thru
a
cooling
range
of
10
F.
Sequence
switches
are
factory
calibrated
and
sealed
and
should
not
require
any
field
changes.
IMPORT
AN
I;
H
a
different
return-water
cooE
mg
lange
or
Iravmg-wuier
control
is
specified,
or
if
brine
below
10
F
b
to
1^
used,
controlkr
must
he
changed.
Consult
local
('arrici
repie-
senlatt\e
tor
proper
control
de\ice
10

Related product manuals