EasyManua.ls Logo

Carrier 30MP - Inputs and Outputs Wiring; Inputs and Outputs Table

Carrier 30MP
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing the controller
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
7
4 Set the communication type and baud rate.
For...
Set Communications
Selection jumper to...
Set DIP switches 1 and 2 to...
Set DIP switches 3 and 4 to...
MS/TP
BACnet MS/TP
The appropriate baud rate. See the
MS/TP Baud
diagram on the
controller.
Off/Off
ARC156
BACnet ARC156
N/A. Baud rate will be 156 kbps
regardless of the DIP switch
settings.
Off/Off
NOTE
Use the same baud rate for all controllers on the network segment.
5 Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration.
6 If the controller is at either end of a network segment, connect a BT485 to the controller.
7 Insert the power screw terminal connector into the controller's power terminals.
8 Verify communication with the network by viewing a Module Status report in the i-Vu® interface.
Wiring inputs and outputs
WARNING
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
See Appendix A (page 30) to print a blank wire list.
Inputs and outputs table
Type
I/O
Terminal
Gnd
Terminal
Point Name/
Function
Hardware/
Signal
Jumper
Position of
Pins
AI
IN-1
2 - Gnd
RH sensor
0-5 Vdc
IN-1
Bottom
AI
IN-2
4 - Gnd
External AI Chilled Water Setpoint
0-5 Vdc
IN-2
Bottom
AI
IN-3
6 - Gnd
Outdoor Air Temperature
10K Thermistor
N/A
Water Header
Temp
AI
IN-4
8 - Gnd
Leaving Chilled Water Header Temperature
5K Thermistor
N/A
Limit
B1
IN-5
1 - Gnd
External Demand Limit Input
Dry Contact
N/A

Table of Contents

Related product manuals