Start-up
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
20
4 Click
CH-2 Linkage Provider
and enter the
Network Number
and a unique
Collector MS/TP Address
for each
30MP chiller UPC Open.
CAUTION
Do not change the 30MP Multi-chiller's
Application Instance
number. It is factory-set in the
controller for each chiller and must match the chiller number. For example, CH-1 is Instance 1, CH-2 is
Instance 2, etc..
5 Click
Accept
.
6 Repeat for each chiller.
7 In the i-Vu® or Field Assistant interface, select the 30MP chiller UPC Open in the navigation tree and go to
Properties
>
Control Program
tab >
Linkage
. On the touchscreen, go to the
Linkage Configuration
screen.
8 Click
Linkage Collector
and set the
Application
Instance
to match the corresponding chiller number
previously assigned above each 30MP chiller UPC's.