Start-up
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
21
Each 30MP UPC Open is factory-set to #1, so you only have to configure chillers CH-2 through CH-8.
Do not change
from 0.
9 Click
.
10 Repeat for each chiller.
Setting the controller
CAUTION Set jumper IN-2 for 0-5 Vdc
. You must change the factory default position of Thermistor/dry
contact. See To wire inputs and outputs (page
10).
Configuring points and properties
You must configure certain points and properties. Appendix C is a complete list of all the points and properties,
with descriptions, defaults, and ranges. These properties affect the unit operation and/or control. Review and
understand the meaning and purpose of each property before changing it.
To start up the controller, configure your necessary points/properties in the following:
• Unit Configuration (page 33)
• Setpoints (page 35
) - Set the
.
• Service Configuration (page 37) - Set the
for entering or leaving water temperature.
• Maintenance (page 40) - To start the plant, set the
to
.