62
Table 10A — 30RB060-190 Electrical Data — Single Point Units
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. All units or modules have single point primary power connection. (Each unit or module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
UNIT 30RB
UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPM
V-Hz (3 Ph)
Supplied MCA MOCP ICF
Rec Fuse
Size
MCA MOCP ICF
Rec Fuse
Size
MCA MOCP ICF
Rec Fuse
Size
Min Max XL XL XL XL XL XL XL XL XL
060
208/230-60 187 253 291.5 350 682.8 350 300.6 350 693.6 350 306.9 350 700.5 350
380-60 342 418 150.9 175 362.9 175 156.0 175 368.8 175 159.0 175 372.6 175
460-60 414 506 127.9 150 302.0 150 132.1 150 306.9 150 135.0 150 310.0 150
575-60 518 633 102.4 125 244.7 110 105.7 125 248.6 125 107.8 125 251.1 125
070
208/230-60 187 253 334.7 400 777.0 400 343.8 400 787.8 400 350.1 400 794.7 400
380-60 342 418 175.5 200 428.8 200 180.8 225 434.7 200 183.6 225 438.5 200
460-60 414 506 147.9 175 355.9 175 152.1 175 360.8 175 155.0 175 363.9 175
575-60 518 633 119.8 150 287.4 150 123.1 150 291.3 150 125.2 150 293.8 150
080
208/230-60 187 253 366.5 400 757.8 400 — — — — 381.9 450 775.5 450
380-60 342 418 189.3 225 401.3 200 — — — — 197.4 225 411.0 225
460-60 414 506 160.6 175 334.7 175 — — — — 167.7 200 342.7 200
575-60 518 633 128.6 150 270.9 150 — — — — 134.0 150 277.3 150
090
208/230-60 187 253 433.6 500 875.9 500 — — — — 449.0 500 893.6 500
380-60 342 418 226.9 250 480.3 250 — — — — 235.0 250 490.0 250
460-60 414 506 191.4 225 399.4 225 — — — — 198.5 225 407.4 225
575-60 518 633 154.6 175 322.2 175 — — — — 160.0 175 328.6 175
100
208/230-60 187 253 472.0 500 914.3 500 — — — — 487.4 500 932.0 500
380-60 342 418 248.7 250 502.1 250 — — — — 256.8 300 511.8 300
460-60 414 506 209.2 250 417.2 225 — — — — 216.3 250 425.2 250
575-60 518 633 170.0 200 337.6 200 — — — — 175.4 200 344.0 200
110
208/230-60 187 253 508.6 600 950.9 600 — — — — 524.0 600 968.6 600
380-60 342 418 265.3 300 518.7 300 — — — — 273.4 300 528.4 300
460-60 414 506 224.1 250 432.1 250 — — — — 231.2 250 440.1 250
575-60 518 633 180.8 200 348.4 200 — — — — 186.2 200 354.8 200
120
208/230-60 187 253 578.1 600 1020.4 600 — — — — 593.5 600 1038.1 700
380-60 342 418 304.6 350 538.0 350 — — — — 312.7 350 567.6 350
460-60 414 506 256.2 300 464.2 300 — — — — 263.3 300 472.2 300
575-60 518 633 208.2 225 325.8 225 — — — — 213.6 225 382.2 225
130
208/230-60 187 253 626.7 700 1068.9 700 — — — — 642.1 700 1086.6 700
380-60 342 418 327.7 350 581.1 350 — — — — 335.8 350 590.8 350
460-60 414 506 276.5 300 484.5 300 — — — — 283.6 300 492.5 300
575-60 518 633 223.3 250 391.0 250 — — — — 228.7 250 397.4 250
150
208/230-60 187 253 684.3 700 1126.5 700 — — — — 699.7 700 1144.2 800
380-60 342 418 360.4 400 613.8 400 — — — — 368.5 400 623.5 400
460-60 414 506 303.2 350 511.2 350 — — — — 310.3 350 519.2 350
575-60 518 633 246.4 250 414.1 250 — — — — 251.8 300 420.5 300
160
208/230-60 187 253 744.8 800 1187.0 800 — — — — 760.2 800 1204.7 800
380-60 342 418 390.1 400 643.5 400 — — — — 398.2 400 653.2 400
460-60 414 506 328.9 350 536.9 350 — — — — 336.0 350 544.9 350
575-60 518 633 265.9 300 433.5 300 — — — — 271.3 300 439.9 300
170
208/230-60 187 253 802.4 1000 1244.6 1000 — — — — 817.8 1000 1262.3 1000
380-60 342 418 422.8 450 676.2 450 — — — — 430.9 450 685.9 450
460-60 414 506 355.6 400 563.6 400 — — — — 362.7 400 571.6 400
575-60 518 633 289.0 300 456.6 300 — — — — 294.4 300 463.0 300
190
208/230-60 187 253 920.5 1000 1362.7 1000 — — — — 935.9 1000 1380.4 1000
380-60 342 418 485.2 500 738.5 500 — — — — 493.3 500 748.2 500
460-60 414 506 408.0 450 616.0 450 — — — — 415.1 450 624.0 450
575-60 518 633 331.5 350 499.1 350 — — — — 336.9 350 505.5 350
AWG — American Wire Gage MOCP — Maximum Overcurrent Protection
ICF — Instantaneous Current Flow XL — Across-the-Line Start
MCA — Minimum Circuit Amps