24
4.8 - Compressor usage and electrical data table
Compressor Reference I Nom I Max
(Un)
I Max
(Un - 10%)
LRA* LRA** 61WG
020 025 030 035 040 045 050 060 070 080 090
SH090 00PSG001482000 10.5 16.1 17.8 98 53.9 1
SH105 00PSG001482100 13.2 19.6 21.6 142 78.1 1 2
SH120 00PSG001482200 13.8 21.1 23.2 142 78.1 1 2
SH140 00PSG001482300 15.6 24.4 26.9 147 80.9 1 2
SH161 00PSG001482400 16.2 26.7 29.4 158 86.9 1 2
SH184 00PSG001482500 20.2 30.9 34.0 197 108.4 1 2
Compressor Reference I Nom I Max
(Un)
I Max
(Un - 10%)
LRA* LRA** 30WG
020 025 030 035 040 045 050 060 070 080 090
WSH090 00PSG001549100 10.6 15.6 17.2 98 53.9 1
WSH105 00PSG001549200 12.9 18.7 20.6 142 78.1 1 2
WSH120 00PSG001549300 13.3 19.8 21.8 142 78.1 1 2
WSH140 00PSG001549400 15.2 23.2 25.6 147 80.9 1 2
WSH161 00PSG001549500 16.5 25.4 28.0 158 86.9 1 2
WSH184 00PSG001549600 19.7 29 31.9 197 108.4 1 2
Compressor Reference I Nom I Max
(Un)
I Max
(Un - 10%)
LRA* LRA** 30WGA
020 025 030 035 040 045 050 060 070 080 090
WSH090 00PSG001549100 11.4 14.7 16.2 98 53.9 1
WSH105 00PSG001549200 13.8 17.7 19.5 142 78.1 1 2
WSH120 00PSG001549300 14.7 19.3 21.3 142 78.1 1 2
WSH140 00PSG001549400 16.5 21.7 23.8 147 80.9 1 2
WSH161 00PSG001549500 18.1 24.1 26.5 158 86.9 1 2
WSH184 00PSG001549600 21.2 27.5 30.3 197 108.4 1 2
Legend
I Nom Nominalcurrentdraw(A)atstandardEuroventconditionsseedenitionofconditionsundernominalunitcurrentdraw)
I Max Maximum operating current, A
LRA* Locked rotor current at nominal voltage, A
LRA** Locked rotor current with electronic starter at nominal voltage, A
Electrical data notes and operating conditions:
• 61WG/30WG/30WGA units have a single power connection point, located
immediatelyupstreamofthemaindisconnectswitch.
• Thecontrolboxincludesthefollowingstandardfeatures:
- a main disconnect switch,
- the starter and motor protection devices for each compressor and the pumps
- the control devices
• Field connections:
All connections to the system and the electrical installations must be in full
accordancewithallapplicablelocalcodes.
• The Carrier 61WG/30WG/30WGA units are designed and built to ensure
conformancewiththesecodes.TherecommendationsofEuropeanstandard
EN 60204-1 (machine safety - electrical machine components - part 1: general
regulations-correspondstoIEC60204-1)arespecicallytakenintoaccount,
whendesigningtheelectricalunitequipment.
NOTES:
• GenerallytherecommendationsofIEC60364areacceptedascompliancewith
therequirementsoftheinstallationdirectives.ConformancewithEN60204-1
isthebestmeansofensuringcompliancewiththeMachinesDirective§1.5.1.
• AnnexBof EN 60204-1describes the electricalcharacteristics used forthe
operationofthemachines.
1. Theoperatingconditionsfortheunitsarespeciedbelow:
Environment*-EnvironmentasclassiedinEN60721(equivalenttoCEI60721):
- Indoorinstallation
- ambienttemperaturerange:+5°Cforthetemperatureminimumto+40°C,
class 4K4H
- humidity range (non-condensing)*:
-50%relativehumidityat40°C
-90%relativehumidityat20°C
- altitude:≤2000m(seenotefortable4.7-Electricaldata,hydronicmodule)
- indoor installation*
- presenceofwater:classAD2(possibilityofwaterdroplets)
- presenceofhardsolids,class4S2(nosignicantdustpresent)
- presenceofcorrosiveandpollutingsubstances,class4C2(negligible)
- vibrationandshock,classAG2,AH2
- competenceofpersonnel,classBA4*(trainedpersonnel-IEC60364)
2. Powersupplyfrequencyvariation:±2Hz.
3. Theneutral(N)conductormustnotbeconnecteddirectlytotheunit(ifnecessary
useatransformer).
4. Over-currentprotectionofthepowersupplyconductorsisnotprovidedwiththe
unit.
5. Thefactory-installeddisconnectswitch(es)/circuitbreaker(s)is(are)ofatype
suitableforpowerinterruptioninaccordancewithEN60947.
6. TheunitsaredesignedforsimpliedconnectiononTN(s)networks(IEC60364).
ForITnetworksprovidealocalearthandconsultcompetentlocalorganisations
to complete the electrical installation. Units delivered with speed drive
(option116T/116Vand270T/270V)arenotcompatiblewithITnetwork.
7. Derivedcurrents:Ifprotectionbymonitoringofderivedcurrentsisnecessaryto
ensure the safety of the installation, the control of the cut-out value must take the
presence of leak currents into consideration that result from the use of frequency
convertersin the unit.A value ofat least 150mA is recommendedto control
differentialprotectiondevices.
NOTE: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should be
considered, always contact your local Carrier representative.
* TheprotectionlevelofthecontrolboxesrequiredtoconformtothisclassisIPX1B
(accordingtoreferencedocumentIEC60529).All61WG/30WG/30WGAunits
fullthisprotectioncondition.
UnitsequippedwithfrontcasingpanelmeetclassIP23.Ifthecasingpanelhas
beenremoved,accesstoenergisedcomponentsisprotectedtolevelIPXXB.