General Parameters General parameters GENUNIT
Temperatures Temperatures TEMP
Pressures Pressures PRESSURE
Inputs Status Inputs status INPUTS
Outputs Status Outputs status OUTPUTS
Pump Status Pump status PUMPSTAT
Run Times Run times RUNTIME
Modes Modes MODES
Setpoint Table Setpoint table SETPOINT
Trendings Trendings TRENDING
Conguration Menu Conguration menu CONFIG
* Depends on the selected language (English by default).
NOTE: Since specic units may not include certain options, some tables may contain parameters that cannot be
congured for a given unit.
GENUNIT – General parameters
No. Status Unit
1 0 to 3 - Local=0 Net.=1 Remote=2
Operating mode:
0 = Local
1 = Network
2 = Remote
2 Run Status
Unit running status: O, Stopping, Delay,
Running, Ready, Override, Tripout, Test, Runtest
3 0 to 1 - Net.: Cmd Start/Stop Unit start/stop via Network
4 0 to 1 - Net.: Cmd Occupied Unit time schedule via Network
5 - min Minutes Left for Start Minutes before the unit start-up
6 Heat/Cool status Heating/cooling status
7 0 to 2 - Heat/Cool Select Heating/cooling selection
8 0=Cool. 1=Heat. 2=Auto
0 = Cooling
1 = Heating
2 = Automatic heating/cooling control
9 0 to 2 - Setpoint Select Setpoint selection
10 0=Auto. 1=Spt1. 2=Spt2
0 = Automatic setpoint selection
1 = Setpoint 1
2 = Setpoint 2
11 0 to 1 - Setpoint Occupied? Setpoint status
12 0 to 100 % Percent Total Capacity Total unit capacity
13 - °C/°F Current Setpoint Current setpoint
14
-20 to 67 °C
Control Point Control point
-4 to 153 °F
15 - A Actual Chiller Current
Actual chiller current, i.e. current delivered by
compressor drives. (Note: This value is not the
total current absorbed by the chiller.)
16 0 to 2000 kW Chiller Power Limit Chiller power limit (Not applicable)
17 - kW Cool. Power (kit hydro) Cooling power (hydronic kit)
18 0 to 1 - Emergency Stop Emergency stop
19 0 to 100 % Active Demand Limit Val Active demand limit value