19
No. Status Unit  
25 - hour Circuit B Fan #3 Hours Operating hours, fan B3
26 - hour Circuit B Fan #4 Hours Operating hours, fan B4
27 - hour Circuit B Fan #5 Hours Operating hours, fan B5
28 - hour Circuit B Fan #6 Hours Operating hours, fan B6
29 - hour Circuit B Fan #7 Hours Operating hours, fan B7
30 - hour Circuit B Fan #8 Hours Operating hours, fan B8
31 - hour Circuit B Fan #9 Hours Operating hours, fan B9
32 - hour Circuit B Fan #10 Hours Operating hours, fan B10
33 - hour Circuit B Fan #11 Hours Operating hours, fan B11
34 - hour Circuit B Fan #12 Hours Operating hours, fan B12
35 - hour Circuit B Fan #13 Hours Operating hours, fan B13
36 - hour Circuit B Fan #14 Hours Operating hours, fan B14
* Depends on the selected language (English by default).
NOTE: The displayed run times are updated every hour.
MODES – Modes
No. Status Unit  
1 no/yes - Start Up Delay In E ect Start-up delay in e ect
2 no/yes - Second Setpoint In Use Second setpoint in use
3 no/yes - Reset In E ect Setpoint reset active
4 no/yes - Demand limit active Demand limit active
5 no/yes - Cooler Pump Rotation Evaporator pump rotation
6 no/yes - Pump Periodic Start Pump periodic start
7 no/yes - Night Low Noise Active Night low noise active
8 no/yes - Master Slave Active Master/slave mode active
9 no/yes - Auto Changeover Active Automatic changeover active
10 no/yes - Condenser Pump Rotation Condenser pump rotation
11 no/yes - Cond Pump Periodic Start Condenser pump periodic start
12 no/yes - Ice Mode In E ect Ice mode active
* Depends on the selected language (English by default).
SETPOINT – Setpoint table
No. Status  Unit  
1
-28.9 to 26 6.7 °C
Cooling Setpoint 1 Cooling setpoint 1
-20.0 to 78.8 44.0 °F
2
-28.9 to 26 6.7 °C
Cooling Setpoint 2 Cooling setpoint 2
-20.0 to 78.8 44.0 °F
3
-28.9 to 26 6.7 °C
Cooling Ice Setpoint Ice storage setpoint
-20.0 to 78.8 44.0 °F
4
0.1 to 11.1 0.6 ^C
Cooling Ramp Loading Cooling ramp loading setpoint
0.2 to 20.0 1.0 ^F
5
26.7 to 63 37.8 °C
Heating Setpoint 1 Heating setpoint 1
80.0 to 145.4 100.0 °F
6
26.7 to 63 37.8 °C
Heating Setpoint 2 Heating setpoint 2
80.0 to 145.4 100.0 °F
7
0.1 to 11.1 0.6 ^C
Heating Ramp Loading Heating ramp loading setpoint
0.2 to 20.0 1.0 ^F
8
3.9 to 50 23.9 °C
Cool Changeover Setpt Cooling changeover setpoint
39.0 to 122.0 75.0 °F
9
0 to 46.1 17.8 °C
Heat Changeover Setpt Heating changeover setpoint
32.0 to 115.0 64.0 °F
10
1 to 20 5 ^C
Varipump Delta Temp Stp Variable speed pump, delta temperature setpoint
1.8 to 36 9.0 ^F
11
50 to 344.8 200 kPa
Varipump Delta Press Stp Variable speed pump, delta temperature setpoint
7.25 to 50 29.0 PSI
12 0 to 100 100 % Switch Limit Setpoint 1 Switch limit setpoint 1
13 0 to 100 100 % Switch Limit Setpoint 2 Switch limit setpoint 2
14 0 to 100 100 % Switch Limit Setpoint 3 Switch limit setpoint 3
*Depends on the selected language (English by default).
NOTE: Since speci c units may not include certain options, some tables provided in the document contain parameters
that cannot be con gured for a given unit. Some con guration or setpoint limits may also be clamped to lower / higher
values depending on option selection.