P0512 P0562 P1012 -1154 P0512 P0562 P1012 -1154
kg 2883 2927 6567 5607 2932 2976 6687 5705
Compressors Semi-hermetic06Tscrewcompressors,50r/s
Circuit A 1 1 1 1 1 1 1 1
Circuit B - - 1 1 - - 1 1
(1)
R-134a
Circuit A kg 140 140 125 110 140 140 125 110
Circuit B kg - - 135 110 - - 135 110
SW220
Circuit A l 32 32 32 32 32 32 32 32
Circuit B l - - 32 32 - - 32 32
Pro-Dialog,electronicexpansionvalves(EXV)
Minimum capacity
(2)
% 30 30 20 20 30 30 20 20
Multi-pipeoodedtype
Net water volume l 70 70 204 183 85 85 224 197
Water connections Victaulic
Inlet/outlet in 6 6 8 8 5 5 6 6
Drainandventconnections(NPT) in 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Maximum water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000
Multi-pipe
Net water volume l 103 103 316 193 103 103 316 193
Water connections Victaulic
Inlet/outlet in 6 6 8 8 6 6 8 8
Drainandventconnections(NPT) in 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Maximum water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000
(1) Weightsareguidelinesonly.Therefrigerantchargeisgivenontheunitnameplate.
(2) Minimumunitcapacitycorrespondstoaphysicalstateoftheunitandisgivenforindicationonly.Theactualcapacityatthisstagedependsonoperatingconditions.
Please refer to chapter 3.
30XW--/30XWH-/30XW-P/30XWHP
Entering temperature at start-up - 35.0°C
Leaving temperature during operation 3.3°C
(1)
15.0°C
Entering/leavingtemperaturedierenceatfullload 2.8K 11.1K
Entering temperature at start-up 13.0°C
(2)
-
Leaving temperature during operation 23.0°C
(2)
63.0°C
Entering/leavingtemperaturedierenceatfullload 2.8K 11.1K
(1) For low-temperature applications, where the leaving water temperature is
below3.3°C,afrostprotectionsolutionmustbeused.Pleaserefertooption5
andoption6.
(2) Forlowercondensertemperaturesawaterowcontrolvalvemustbeusedat
thecondenser(twoorthree-wayvalve).Pleaserefertooption152toensure
thecorrectcondensingtemperature.
Ambienttemperatures:Duringstorageandtransportofthe30XWunits
(includingbycontainer)theminimumandmaximumpermissibletemperaturesare
-20°Cand72°C(and65°Cforoption200).
Evaporatorleavingwatertemperature,°C
Condenserleavingwatertemperature,°C,
Fromapprox.60%tofullload
Partloadlimitapprox.50%
Minimumloadlimitapprox.30%
5
10
15
20
25
30
35
40
45
50
55
60
65
70
0510 15
Units with the medium temperature (option 5) or low
temperature (option 6) option allow glycol solution
production down to:
• - 6°C with ethylene glycol and option 5 (minimum
weight concentration of 25%)
• - 3°C with propylene glycol and option 5 (minimum
weight concentration of 24%)
• - 12°C with ethylene glycol and option 6 (minimum
weight concentration of 35%)
• - 8°C with propylene glycol and option 6 (minimum
weight concentration of 30%)
These options are available for the following unit reference
numbers:
30XW- P0512
30XW- P0562
30XW- P1012
30XW--1154
Option 100C (evaporator with one pass) is not compatible
with options 5 and 6. For option 5 the evaporator must be
congured with two passes and for option 6 with three passes.
Formoreprecisedetailsrefertotheunitselectionprogram.