PUMPSTAT – Pump status
No. Status Unit
Displayed text* Description
1 no/yes - Cooler Flow Setpoint Out Evaporator ow setpoint output
2 0 to 1 - Cooler Pump #1 Command Evaporator pump 1 control
3 0 to 1 - Cooler Pump #2 Command Evaporator pump 2 control
4 0 to 1 - Rotate Cooler Pumps ? Evaporator pumps rotation
5 open/close - Cooler Flow Switch Evaporator ow switch
6 0 to 1 - Condenser Pump Command1 Condenser pump 1 control
7 0 to 1 - Condenser Pump Command2 Condenser pump 2 control (not available!)
8 0 to 1 - Rotate Condenser Pumps ? Condenser pumps rotation (not available!)
9 - kPa Water pres before cooler Evaporator entering water pressure
10 - kPa Water pres after cooler Evaporator leaving water pressure
11 - kPa Water pres before lter Filter entering water pressure
12 - kPa Water pres after lter Filter leaving water pressure
13 - l/s Water ow Water ow rate
14 - kW Cooling power Cooling power
15 open/close - Condenser Flow Status Condenser ow status
*Depends on the selected language (English by default).
RUNTIME – Run times
No. Status Unit Displayed text* Description
1 - hour Machine Operating Hours Unit operating hours
2 - - Machine Starts Number Number of unit starts
3 - hour Compressor A Hours Operating hours, compressor A
4 - - Compressor A Starts Number of starts, compressor A
5 - hour Compressor B Hours Operating hours, compressor B
6 - - Compressor B Starts Number of starts, compressor B
7 - hour Compressor C Hours Operating hours, compressor C
8 - - Compressor C Starts Number of starts, compressor C
9 - hour Cooler Pump #1 Hours Operating hours, evaporator pump 1
10 - hour Cooler Pump #2 Hours Operating hours, evaporator pump 2
11 - hour Condenser Pump #1 Hours Operating hours, condenser pump 1
12 - hour Condenser Pump #2 Hours Operating hours, condenser pump 2 (not available!)
13 - hour Free Cool A Pump Hours Pump operating hours in Free Cooling, circuit A
14 - hour Free Cool B Pump Hours Pump operating hours in Free Cooling, circuit B
* Depends on the selected language (English by default).
NOTE: The displayed run times are updated every hour.
MODES – Modes
No. Status Unit Displayed text* Description
1 no/yes - Start Up Delay In Eect Start-up delay in eect
2 no/yes - Second Setpoint In Use Second setpoint in use
3 no/yes - Reset In Eect Setpoint reset active
4 no/yes - Demand limit Active Demand limit active
5 no/yes - Ramp Loading Active Ramp loading active
6 no/yes - Cooler Heater Active Evaporator heater active
7 no/yes - Cooler Pump Rotation Evaporator pump rotation
8 no/yes - Pump Periodic Start Pump periodic start active
9 no/yes - Night Low Noise Active Night low noise active
10 no/yes - Master Slave Active Master/slave mode active
11 no/yes - Auto Changeover Active Automatic changeover active
12 no/yes - Heating Low EWT Lockout Heating low EWT lockout
13 no/yes - Condenser Pump Rotation Condenser pump rotation (not available!)
14 no/yes - Cond Pump Periodic Start Condenser pump periodic start
15 no/yes - Ice Mode In Eect Ice storage mode active
16 no/yes - Defrost Active On Cir A Defrost mode active, circuit A
17 no/yes - Defrost Active On Cir B Defrost mode active, circuit B
18 no/yes - Free Cooling Active Free cooling mode active
19 no/yes - Reclaim Active Reclaim mode active
20 no/yes - Low Suction Circuit A Low suction, circuit A
21 no/yes - Low Suction Circuit B Low suction, circuit B
22 no/yes - Low Suction Circuit C Low suction, circuit C
23 no/yes - Map compressor Circuit A Compressor mapping, circuit A
24 no/yes - Map compressor Circuit B Compressor mapping, circuit B
25 no/yes - Map compressor Circuit C Compressor mapping, circuit C