Table 1 — TEMP System Thermostat Categories and Options
OPTION DESCRIPTION DEFAULT MINIMUM MAXIMUM
CATEGORY 1.0 SET POINTS
1.1
Cooling Set Point Low Limit (F) 68 50 99
1.2
Heating Set Point High Limit (F) 75 50 99
1.3
Unoccupied Cooling Set Point (F) 80 50 99
1.4
Unoccupied Heating Set Point (F) 65 50 99
1.5
Rotating Display OFF OFF ON
1.6
Fahrenheit Temperature Display ON OFF ON
CATEGORY 2.0 OCCUPANCY SCHEDULE
2.1-2.8
Occupancy Period 1-8
Days Active
Start Time
Stop Time
MTWTF
06:00 AM
06:00 PM
NONE
12:00 AM
12:00 AM
MTWTFSSH
11:59 PM
11:59 PM
2.9
Schedule Number 0 0 99
2.10
Override Time Limit (Hours) 1 0 4
CATEGORY 3.0 DAMPER
No configuration required.
CATEGORY 4.0 HVAC EQUIPMENT
4.1
Fan Operation For Heat ON OFF ON
4.2
Time Guard Between Modes ON OFF ON
4.3
Time Guard Override OFF OFF ON
4.4
LAT (Leaving-Air Temperature) Monitoring ON OFF ON
4.5
First Stage Cooling Temperature Limit (F) 45 40 45
4.6
Second Stage Cooling Temperature Limit (F) 50 45 50
4.7
First Stage Heating Temperature Limit (F) 110 110 180
4.8
Second Stage Heating Temperature Limit (F) 105 105 160
4.9
Auxiliary Relay (0 — No Control, 1 — Occupied Schedule,
2 — IAQ, 3 — Reversing Valve, 4 — Economizer)
004
4.10
Optimize Staging ON OFF ON
4.11
Cooling Temperature Lockout OFF OFF ON
4.12
Cooling Lockout Set Point (F) 40 10 80
4.13
Heating Temperature Lockout OFF OFF ON
4.14
Heating Lockout Set Point (F) 60 10 80
4.15
Minimum Heat Run Time (Minutes) 3 1 30
4.16
Minimum Cool Run Time (Minutes) 3 1 30
4.17
Pre-Occupancy Purge OFF OFF ON
4.18
Fan Switch Control (0 — Use Fan Switch Position,
1 — Fan Switch ON, 2 — Fan Switch AUTO)
002
4.19
Cool Switch Control (0 — Use Cool Switch Position, 1 — Cool
Switch AUTO, 2 — Cool Switch OFF)
002
4.20
Heat Switch Control (0 — Use Heat Switch Position, 1 — Heat
Switch AUTO, 2 — Heat Switch OFF)
002
CATEGORY 5.0 SENSORS
5.1
Room Sensor (1 — Local Room Sensor, 2 — Remote Room
Sensor, 3 — Average Local Sensor and Remote Room Sensor)
113
5.2
Zone Temperature Sensor Calibration (F) Zone Temp. 30 180
5.3
Remote Room Sensor Calibration (F) Room Temp. 30 180
5.4
Supply-Air Temperature Sensor OFF OFF ON
5.5
Supply-Air Temperature Sensor Calibration (F) Duct Temp. 30 180
5.6
DX Coil Temperature Sensor OFF OFF ON
5.7
DX Coil Temperature Sensor Calibration (F) Coil Temp. 30 180
5.8
Outdoor-Air Temperature Sensor (OAT) OFF OFF ON
5.9
Outdoor-Air Temperature Sensor Calibration (F) Outdoor Temp. –40 150
Fig. 6 — TEMP System Thermostat
Display Screen
Fig. 7 — TEMP System Thermostat
Configuration Buttons