Table 1 — TEMP System Thermostat Categories and Options (cont)
OPTION DESCRIPTION DEFAULT MINIMUM MAXIMUM
5.10
Fan Status Switch OFF OFF ON
5.11
Humidity Sensor/Filter Status (0 — No Sensor, 1 — Indoor Humidity
Sensor, 2 — Filter Status Switch)
002
5.12
Humidity Sensor Calibration Indoor Humidity 0 100
CATEGORY 6.0 SUPPLEMENTAL HEAT
No configuration needed.
CATEGORY 7.0 DIAGNOSTICS/METERING
7.1
Error Code Display OFF OFF ON
7.2
Communication Check OFF OFF ON
7.3
Alternate Information OFF OFF ON
7.4
Comfort Trend Demand (1/10° F) 0 0 25.5
7.5
Comfort Trend Time Limit (Minute) 2 2 255
7.6
HVAC Usage Meter OFF OFF ON
7.7
Override Usage Meter OFF OFF ON
7.8
HVAC Override Usage Meter OFF OFF ON
7.9
Heating Mode Error Set Point (F) 0 0 140
7.10
Cooling Mode Error Set point (F) 140 0 140
7.11
Unit Reset OFF OFF ON
CATEGORY 8.0 START-UP
8.1
Device Element Address 0 0 239
8.2
Security Level (1 — All Programming Allowed, 2 — Programming of
Occupancy Schedules and Set Points Only, 3 — Programming of
Set Points Only, 4 — No Programming Allowed)
114
8.3
Device Bus Number 0 0 239
CATEGORY 9.0 BROADCAST/DAYLIGHT SAVINGS TIME
9.1
Broadcast Acknowledger OFF OFF ON
9.2
Global Schedule Broadcast OFF OFF ON
9.3
Network Time Request OFF OFF ON
9.4
Receive Network Time ON OFF ON
9.5
Network Time Broadcast OFF OFF ON
9.6
Daylight Savings Time Start Month 4 1 12
9.7
Daylight Savings Time Start Week 1 1 5
9.8
Daylight Savings Time Start Day 7 1 7
9.9
Daylight Savings Time Added Minutes 60 0 90
9.10
Daylight Savings Time Stop Month 10 1 12
9.11
Daylight Savings Time Stop Week 5 1 5
9.12
Daylight Savings Time Stop Day 7 1 7
9.13
Daylight Savings Time Subtracted Minutes 60 0 90
CATEGORY 10.0 HOLIDAY SCHEDULES
10.1-10.18
Holiday Schedule 1-18
Holiday Start Month
Start Day
Duration (Days)
0
0
0
0
0
0
12
31
99
CATEGORY 11.0 ALARM
11.1
Equipment Priority 7 0 7
11.2
Communication Failure Retry Time (Minutes) 10 1 240
11.3
Re-Alarm Time (Minutes) 30 1 255
CATEGORY 12.0 OPTIMAL START
12.1
Optimal Start Time Limit (Hrs) 4 0 4
CATEGORY 13.0 LOADSHED
13.1
Demand Limit Group Number 0 0 16
CATEGORY 14.0 INDOOR-AIR QUALITY (IAQ)
14.1
System Indoor Air Quality Sensor OFF OFF ON
14.2
Indoor-Air Quality Economizer Delay (Minutes) 10 5 30
14.3
Indoor-Air Quality Maximum Space Temperature Reset (F) 2 0 10
14.4
Indoor-Air Quality Humidity Lockout Set Point 0 0 100
14.5
Indoor-Air Quality Low Temperature Lockout (F) (OAT) 45 0 110
14.6
Indoor-Air Quality High Temperature Lockout (F) (OAT) 80 0 110
14.7
Indoor-Air Quality Alarm Delay (Minutes) 0 0 240