Table 3 Advanced Setup Configuration
Install Accessories The Add-A-Wire™ accessory
can be used with this thermostat. The remote temperature
sensor (33CSSEN-WB), outdoor-rated temperature sensor
(33CSSEN-01), and the duct sensor (33CSSEN-DS) can be
used with this thermostat.
Refer to the individual accessory installation instructions for
more information.
Program Thermostat Schedules Before program-
ming the thermostat, plan the thermostat daily schedule. The
schedule is divided into 7 days (Monday through Sunday).
Each day has from 2 to 4 time periods (Occupied 1, Occupied
2, Occupied 3, Unoccupied) depending on the configuration of
the thermostat. Each occupied time period has a start time, stop
time, heating set point, and cooling set point. The unoccupied
time period has a heating set point and a cooling set point. The
unoccupied time period is active whenever an occupied time
period is not active. Fill in Table 4 as an aid to programming
the daily schedules.
PROGRAMMING MODE To program the daily sched-
ules, perform the following procedure:
1. Enter Programming mode by pressing and holding the
Mode and UP ARROW buttons. The Occupied 1 annun-
ciator will appear on the thermostat display. Use the
UP ARROW and DOWN ARROW buttons to set the
maximum number of Occupied periods for each day. The
thermostat can be set to 1, 2, or 3. After the number of
Occupied periods has been selected, press the Mode but-
ton. See Fig. 8.
2. The cooling set point for Occupied 1 will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the cooling set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C). Press the Mode button to continue. See
Fig. 8.
3. The heating set point for Occupied 1 will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the heating set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C). Press the Mode button to continue. See
Fig. 8.
4. The cooling set point for Unoccupied will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the cooling set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C) or “OF” (no unoccupied cooling). To
configure the Unoccupied Cooling set point to OF, press
the DOWN ARROW button until 35 F (2 C) is displayed.
Press the DOWN ARROW button again to display OF.
Press the Mode button to continue.
5. The heating set point for Unoccupied will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the heating set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C). Press the Mode button to continue.
6. The day of the week will be shown. Use the UP ARROW
and DOWN ARROW buttons to change the day of the
week until the desired starting day is shown. Possible
choices are Mo (Monday) through Su (Sunday). Press the
Mode button when the desired day is shown.
7. The Start Time for Occupied 1 will be displayed. Use the
UP ARROW and DOWN ARROW buttons to raise or
lower the time until the desired Start Time is shown. Press
the Mode button to continue. See Fig. 9.
8. The Stop Time for Occupied 1 will be displayed. Use the
UP ARROW and DOWN ARROW buttons to raise or
lower the time until the desired Stop Time is shown. Press
the Mode button to continue.
9.TheON/OFFiconwillbedisplayed.UsetheUP
ARROW to turn the Occupied 1 period ON for this day.
Use the DOWN ARROW to turn the Occupied 1 period
OFF for this day.
10. Repeat Steps 2 through 9 to program the remaining
schedule for Occupied periods 2 and 3.
Table 4 Daily Schedule Planner
NOTE: The cooling temperature set point must be higher than the heating temperature set point. (The temperature difference may be changed in
the advanced set up configuration.)
STEP DESCRIPTION RANGE DEFAULT
1 Time of Day (Clock) 24 Hour 12:00 AM
2 Day of Week Su - Sa Mo
3 Display Blanking OFF/ON ON
4 Single/Dual Set Point 1, 2 2
5 2 or 4 Pipe System 2, 4 4
6
2-Pipe System
Operation
1-5 3
7 Fan Operation OFF/ON ON
8 Deadband 1-6 degrees 2
9
Set Point Minimum
Temperature Difference
0 - 6 degrees 2
10
Thermoglow™
Backlight
OFF/ON OFF
11 Temperature Units F/C F
12 Remote Sensor Setup YES/NO YES
13 Override Time Duration 0-6 hours 2 hours
14 Dry Contact Switch NO/NC NO
15
Dry Contact Switch
Operation
Occupied,
Unoccupied
Occupied
16
Dry Contact Switch
Unoccupied Operation
Off, Set Points Set Points
DAY
OF THE
WEEK
SCHEDULE
Occupied 1 Occupied 2 Occupied 3 Unoccupied
Start / Stop / Heat / Cool Start / Stop / Heat / Cool Start / Stop / Heat / Cool Heat / Cool
Monday /// /// /// /
Tuesday /// /// /// /
Wednesday /// /// /// /
Thursday /// /// /// /
Friday /// /// /// /
Saturday /// /// /// /
Sunday /// /// /// /